Test Operation
SiBE37-701
184
Test Operation
3.2Possible settings for function C
The noise of level 3 < level 2 < level 1 (
).
(a) This setting = factory setting
3.3Possible settings for function D and E
For function D (
) only: the noise of level 3 < level 2 < level 1 (
).
For function E (
) only: the power consumption of level 1< level 2 < level 3 (
).
(a) This setting = factory setting
3.4Possible settings for function H
The evaporating temperature level H (high) < level M (medium) < level L (low) (
).
(a) This setting = factory setting
4. Push the
button and the setting is defined.
5. When the
button is pushed again, the operation starts according to the setting.
Refer to the service manual for more details and for other settings.
Confirmation of the set mode
The following items can be confirmed by setting mode 1 (H1P LED is off)
Check the LED indication in the field marked
.
1. Indication of the present operation state
-
h
, normal
-
i
, abnormal
-
j
, under preparation or under test operation
2. Indication of low noise operation state
-
h
standard operation (= factory setting)
-
i
operation
3. Indication of power consumption limitation setting
-
h
standard operation (= factory setting)
-
i
operation
1.2.6.4
Test operation
Do not insert fingers, rods or other objects into the air inlet or outlet. When the fan is
rotating at high speed, it will cause injury.
Do not perform the test operation while working on the indoor units.
When performing the test operation, not only the outdoor unit, but the connected indoor unit will
operate as well. Working on a indoor unit while performing a test operation is dangerous.
H1P H2P H3P H4P H5P H6P H7P
(a)
i
h
h
h
h
h
h
i
h
h
h
h
h
jc
i
h
h
h
h
j
h
i
h
h
h
h
j
j
H1P H2P H3P H4P H5P H6P H7P
i
h
h
h
h
h
j
(a)
i
h
h
h
h
j
h
i
h
h
h
j
h
h
H1P H2P H3P H4P H5P H6P H7P
i
h
h
h
h
h
j
(a)
i
h
h
h
h
j
h
i
h
j
h
h
h
h
1
OFF
1
2
3
L.N.O.P
1
DEMAND
3
1
2
3
L
H
M
L
BS3 RETURN
BS3 RETURN
H1P H2P H3P H4P H5P H6P H7P
h
h
i
h
h
h
h
H1P H2P H3P H4P H5P H6P H7P
h
h
i
h
h
h
h
H1P H2P H3P H4P H5P H6P H7P
h
h
i
h
h
h
h
L.N.O.P
L.N.O.P
DEMAND
DEMAND
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...