Basic Control
SiBE37-701
106
Function
2.2
Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
[Heating operation]
Rotation of outdoor units
In order to make operating time equal for each compressor of multi connection outdoor units,
outdoor units are used in rotation.
However this is not applicable to single units.
[Rotation of outdoor units]
[System with two outdoor units]
[System with three outdoor units]
[Timing of outdoor rotation]
In start of startup control
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te : Low pressure equivalent saturation
temperature (°C)
Te set value (Make this setting while in Setting
mode 2.)
TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
*On multi-outdoor-unit systems, this control is made
according to values of the first-priority unit, which is
detected with the pressure sensor.
Te setting
L
M (Normal)
(factory
setting)
H
3
6
7
8
9
10 11
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc : High pressure equivalent saturation
temperature (°C)
Te set value (Make this setting while in Setting
mode 2.)
TcS : Target Tc value
(Varies depending on Tc setting, operating
frequency, etc.)
*On multi-outdoor-unit systems, this control is made
according to values of the first-priority unit, which is
detected with the pressure sensor.
Tc setting
L
M (Normal)
(factory
setting)
H
43
46
48
Outdoor Unit 1
Outdoor Unit 2
Previous time
Priority 1
Priority 2
This time
Priority 2
Priority 1
Next time
Priority 1
Priority 2
Outdoor Unit 1
Outdoor Unit 2
Outdoor Unit 3
Previous time
Priority 1
Priority 2
Priority 3
This time
Priority 3
Priority 1
Priority 2
Next time
Priority 2
Priority 3
Priority 1
One time after the
next
Priority 1
Priority 2
Priority 3
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...