Daikin VRV III REMQ8P8Y1B Installation Manual Download Page 9

REMQ8~16P8Y1B
VRVIII System air conditioner
4PW40598-1A

Installation manual

4

4.

I

NSPECTING

 

AND

 

HANDLING

 

THE

 

UNIT

At delivery, the packing should be checked and any damage should
be reported immediately to the carrier claims agent.

When handling the unit, take into account the following:

1

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor

damage.

2

Choose on beforehand the path along which the unit is to be
brought in.

3

Bring the unit as close as possible to its final installation position
in its original package to prevent damage during transport. 

(See

figure 4)

4

Lift the unit preferably with a crane and 2 belts of at least 8 m
long. 

(See figure 4)

Always use protectors to prevent belt damage and pay attention
to the position of the unit's centre of gravity.

5

If a forklift is to be used, preferably transport the unit with pallet
first, then pass the forklift arms through the large rectangular
openings on the bottom of the unit. 

(See figure 5)

5.1 From the moment you use a forklift to move the unit to its final

position, lift the unit under the pallet.

5.2 Once at final position, unpack the unit and pass the forklift arms

through the large rectangular openings on the bottom of the unit.

5.

U

NPACKING

 

AND

 

PLACING

 

THE

 

UNIT

Remove the four screws fixing the unit to the pallet.

Make sure the unit is installed level on a sufficiently strong base
to prevent vibration and noise.

The height of the foundation must at least be 150 mm from the
floor.

The unit must be installed on a solid longitudinal foundation
(steelbeam frame or concrete) and make sure the base under
the unit is larger than the grey marked area as indicated in

figure 3

.

Fasten the unit in place using four
foundation bolts M12. It is best to screw in
the foundation bolts until their length
remains 20 

mm above the foundation

surface.

1

Packaging material

2

Opening (large)

3

Belt sling

4

Opening (small) (40x45)

5

Protector

NOTE

Use a belt sling of 

20 mm wide that adequately

bears the weight of the unit.

NOTE

Use filler cloth on the forklift arms to prevent
damaging the unit. If the paint on the bottom
frame peels off, the anti corrosion effect may
decrease.

Do not use stands to only support the corners. 

(See

figure 8)

1

Hole for foundation bolt

2

Inner dimension of the base

3

Distance between foundation bolt holes

4

Depth of unit

5

Outher dimension of the base

A

Longitudinal foundation dimension

B

Distance between foundation bolt holes

Model

A

B

REMQ8~12

930

792

16

1240

1102

Prepare a water drainage channel around the
foundation to drain waste water from around the unit.

If the unit is to be installed on a roof, check the
strength of the roof and its drainage facilities first.

If the unit is to be installed on a frame, install the
waterproofing board within a distance of 150 mm
under the unit in order to prevent infiltration of water
coming from under the unit.

When installed in a corrosive
environment, use a nut with
plastic washer (1) to protect the
nut tightening part from rust.

X

Not allowed

O

Allowed (units: mm)

20 mm

1

Summary of Contents for VRV III REMQ8P8Y1B

Page 1: ...INSTALLATION MANUAL REMQ8P8Y1B REMQ10P8Y1B REMQ12P8Y1B REMQ14P8Y1B REMQ16P8Y1B System air conditioner ...

Page 2: ...m b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 300 mm e 20 mm f 500 mm a 50 mm b 100 mm c 50 mm d 100 mm e 10...

Page 3: ...20 mm 500 mm 1 1 1 A B 2 2 2 4 5 3 8 F1 F2 F1 F2 Q1 Q2 F1 F1 F2 F2 Q1Q2 7 TOIN DUNIT TOOUT DUNIT TOMULTIUNIT A1P Q1 Q2 A1P Q1 Q2 A1P 1 2 2 3 4 5 6 8 10 10 9 9 REMQ8 12 REMQ14 16 1 2 3 4 1 5 6 7 8 F1 F2F1F2 F1 F2F1F2 TO IN D UNIT TO OUT D UNIT TO IN D UNIT TO OUT D UNIT F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 11 10 10 9 9 12 13 14 15 16 17 18 20 19 21 ...

Page 4: ...ään ohjeidemme mukaisesti 14 za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům 15 u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják 17 spe...

Page 5: ...štelę 23 Maksimālais pieļaujamais spiediens PS K bar Minimālā maksimālā pieļaujamā temperatūra TS TSmin Minimālā temperatūra zemā spiediena pusē L C TSmax Piesātinātā temperatūra saskaņā ar maksimālo pieļaujamo spiedienu PS M C Dzesinātājs N Spiediena drošības ierīces iestatīšana P bar Izgatavošanas numurs un izgatavošanas gads skat modeļa izgatavotājuzņēmuma plāksnītie 24 Maximálny povolený tlak ...

Page 6: ...pes will cause malfunctions when combined with the REYQ P system The REMQ P units can be combined with Daikin VRV indoor units for air conditioning purposes suitable for R410A The present installation manual describes the procedures for unpacking installing and connecting the REMQ P units Installation of the indoor units is not described in this manual Always refer to the installation manual suppl...

Page 7: ...350 910 REYQ30 REMQ14 REMQ16 375 975 REYQ32 REMQ16 REMQ16 400 1040 REYQ34 REMQ8 REMQ10 REMQ16 425 1105 REYQ36 REMQ8 REMQ12 REMQ16 450 1170 REYQ38 REMQ10 REMQ12 REMQ16 475 1235 REYQ40 REMQ12 REMQ12 REMQ16 500 1300 REYQ42 REMQ10 REMQ16 REMQ16 525 1365 REYQ44 REMQ12 REMQ16 REMQ16 550 1430 REYQ46 REMQ14 REMQ16 REMQ16 575 1495 REYQ48 REMQ16 REMQ16 REMQ16 600 1560 NOTE When installing a multi outdoor sy...

Page 8: ...oncentration from exceeding allowable safety limits in the event of a refrigerant leak 11 To prevent dripping water to form a puddle underneath the unit install a drain pan available as option kit Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smoke ...

Page 9: ...height of the foundation must at least be 150 mm from the floor The unit must be installed on a solid longitudinal foundation steelbeam frame or concrete and make sure the base under the unit is larger than the grey marked area as indicated in figure 3 Fasten the unit in place using four foundation bolts M12 It is best to screw in the foundation bolts until their length remains 20 mm above the fou...

Page 10: ... be installed by a licensed refrigeration technician and must comply with relevant local and national regulations Caution to be taken when brazing refrigerant piping Do not use flux when brazing copper to copper refrigerant piping Particularly for the HFC refrigerant piping Therefore use the phosphor copper brazing filler metal BCuP which does not require flux Flux has extremely harmful influence ...

Page 11: ... around the edges using repair paint to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage 1 Large knockout hole 2 Small knockout hole 3 Drill 4 Points for drilling Any gas remaining inside the stop valve may blow off the pinched piping causing damage or injury 1 Pinched piping 2 Do not dissolve this brazing 3 Auxiliary ...

Page 12: ...ohibited patterns change to pattern 1 or 2 To avoid the risk of oil retention to the outmost outdoor unit always connect the stop valve and the piping between outdoor units as shown in the 4 correct possibilities of the figure below Prohibited patterns change to pattern 1 or 2 Change to configuration as in figures below Correct configuration If the piping length between the outdoor units exceeds 2...

Page 13: ... installation may lead to malfunction of the outdoor unit 5 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level difference and allowable length after branching as indicated in 6 6 Example of connection on page 9 6 5 Protection against contamination when installing pipes Take measures to prevent foreign materi...

Page 14: ...Outdoor unit multi connection piping kit and refrigerant branch kit selection How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side choose from the following table in accordance with the capacity of the outdoor unit example refnet joint A How to select the refnet header Choose from the following table in accordance with the total capacity of...

Page 15: ...it can be extended up to 90 m if all the following conditions are fulfilled Required conditions Example drawings It is necessary to increase the pipe size of the liquid and suction gas pipe if the pipe length between the first and the final branch kit is over 40 m reducers must be procured on site Increasing the HP LP gas pipe size is not allowed If the increased liquid pipe size is larger than th...

Page 16: ... Liquid line stop valve 11 Refrigerant charge port 12 Valve A 13 Valve B 14 Valve C 15 To BS unit or indoor unit 16 Stop valve 17 Service port 18 Field piping 19 Gas flow NOTE Make sure to perform airtightness test and vacuum drying using the service ports of the stop valves of the equalizer pipe HP LP gas pipe suction gas pipe and liquid pipe For the service port location refer to the Caution lab...

Page 17: ...quid H E liquid suction liquid R10 Resistor current sensor A4P A8P R31T R33T Thermistor discharge M1C M3C R50 R59 Resistor R90 Resistor current sensor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high SD1 Safety devices input T1A Current sensor A6P A7P V1R Diode bridge A3P V1R Power module A4P A8P V2R Power module A3P X1A X4A Connecto...

Page 18: ...e to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrical charge due to leaked electrical current which will have to be discharged with the grounding Be sure to install an earth leakage breaker One that can handle...

Page 19: ...ing wires to the terminal block on the PC board too much heat or tightening could damage the PC board Attach with care See the table below for the tightening torque of the transmission wiring terminals 1 Field power supply 6 Remote controller 2 Main switch 7 BS unit 3 Earth 8 Cool heat selector 4 Outdoor unit 9 Earth leakage breaker 5 Indoor unit 10 Fuse Power supply wiring sheathed cable 380 415 ...

Page 20: ... wiring between outdoor units 1 Liquid pipe 2 HP LP gas pipe 3 Finishing tape 4 Suction gas pipe 5 Transmission wiring 6 Insulation material 1 Power supply 380 415 V 3 N 50 Hz 2 Earth leakage breaker 3 Fuse 4 Grounding wire 5 Power supply terminal block 6 Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N 7 Ground wire GRN YLW 8 Clamp the power wire to the plastic bracket using a f...

Page 21: ...n page 5 The electrical work 1 Make sure there is no faulty power wiring or loose nuts See 8 Field wiring on page 11 2 Make sure there is no faulty transmission wiring or loose nuts See 8 Field wiring on page 11 3 Make sure the insulation resistance of the main power circuit is not deteriorated Measure the insulation resistance and check if the value is in accordance with relevant local and nation...

Page 22: ...ve Refrigerant cannot be charged until all field wiring and field piping has been completed Refrigerant may only be charged after performing the leak test and the vacuum drying The refrigerant charge of the system must be less than 100 kg This means that in case the calculated refrigerant charge is equal to or more than 95 kg you must divide your multiple outdoor system into smaller independent sy...

Page 23: ... 1 H1P x OFF BS1 MODE BS1 MODE BS2 SET BS2 SET BS3 RETURN BS1 MODE Adding refrigerant using the automatic refrigerant charging function is recommended When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your eyes when charging refrigerant When the refrigerant charging procedure is done or when pausing close the valve of the...

Page 24: ...trument 2 Refrigerant tank R410A siphon system 3 Charge hose 4 Equalizer pipe stop valve 5 High pressure low pressure gas pipe stop valve 6 Suction gas pipe stop valve 7 Liquid pipe stop valve 8 Refrigerant charge port 9 Valve A 10 Valve B 11 Valve C 12 To BS unit indoor unit 13 Stop valve 14 Service port 15 Field piping 16 Refrigerant flow when pre charging through the liquid stop valve service p...

Page 25: ...system reaches the stable state It may disturb a correct decision and may cause overcharging 7 Ready Press the button once within 5 minutes If the button is not pushed within 5 minutes P2 will be displayed on the remote controller Refer to 3 Remote controller malfunction code display on page 21 8 Operation When the following LED display is shown open valve A and close the front panel If the front ...

Page 26: ...nt charging operation If the refrigerant tank is left with the valve open the amount of refrigerant which is properly charged may be off the point H1P H2P H3P H4P H5P H6P H7P w c c w w w w LED display Default status before delivery Micro computer operation monitor Mode Ready Error Cooling Heating changeover Low noise Demand Multi Indivi dual Bulk master Bulk slave HAP H1P H2P H3P H4P H5P H6P H7P H...

Page 27: ...x 15 70 x 75 w x x w w w w 16 75 x 80 w x w x x x x 17 80 x 85 w x w x x x w 18 85 x 90 w x w x x w x 19 90 x 95 w x w x x w w 20 95 x 100 w x w x w x x 21 100 x w x w x w x w NOTE If you get confused in the middle of the input process press the button to return to setting mode 1 initial state The H1P LED is off x Resume the input procedure from step 2 onwards BS2 SET BS3 RETURN BS2 SET BS3 RETURN...

Page 28: ... is located on the outdoor unit PCB A1P The figure shows state of the LED indications when the unit is shipped from the factory Check operation procedure 1 Turn the power on for the outdoor unit and the indoor unit Be sure to turn the power on at least 6 hours before operation in order to have power running to the crankcase heater 2 Make sure that transmission is normal by checking the LED display...

Page 29: ...normal w abnormal c under preparation or under test operation 2 Indication of low noise operation state x standard operation factory setting w operation 3 Indication of power consumption limitation setting x standard operation factory setting w operation NOTE If you get confused in the middle of the setting process push the button Then it returns to setting mode 1 H1P LED is off Possible functions...

Page 30: ...ing the test operation the refrigerant running sound or the magnetic sound of a solenoid valve may become loud and the LED display may change but these are not mal functions During the test operation it is not possible to stop the unit operation from a remote controller To abort the operation press the button The unit will stop after 30 seconds 6 Close the front panel in order to let it not be the...

Page 31: ...g 4 When the unit is not operating push the button until the additional refrigerant charging operation function A in setting mode 2 can be defined refer to Setting the mode on page 24 the H1P LED is on w 5 The operation starts automatically The H2P LED will start flashing c and the messages Test operation and Under centralized control will display on the remote controller 6 After charging the spec...

Page 32: ... as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum concentration...

Page 33: ...0 3 2 6 6 6 6 23 18 9 8 1 2 4 3 5 13 14 15 10 7 12 19 2 1 24 6 11 16 17 15 6 5 10 11 12 7 4 9 16 17 18 3 8 13 14 2 2 1 1 9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 4 4 6 6 6 6 6 6 22 23 24 ...

Page 34: ...4PW40598 1A Copyright Daikin ...

Reviews: