Other Control
Si39-306
86
Function
5.2
Emergency Operation
If the compressor cannot operate, this control inhibits any applicable compressor or outdoor unit
from operating to perform emergency operation only with the operative compressor or outdoor
unit.
5.2.1 Restrictions for Emergency Operation
• In the case of system with 1 outdoor unit installed and when the inverter compressor is set to
operation prohibit, only when thermostats of indoor units having a capacity of 50% or more of
the outdoor unit capacity turn ON, the emergency operation is functional. (If the total capacity
of indoor units with thermostat ON is small, the outdoor unit cannot operate.)
• If the emergency operation is set while the outdoor unit is in operation, the outdoor unit stops
once after pump-down residual operation (a maximum of 5 minutes elapsed).
5.2.2 In the Case of 1-Outdoor-Unit System (REYQ8 to 16M)
•
Emergency operation with settings in service mode
∗
“Inhibition of operation” is set with each compressor.
• To inhibit INV compressor from operating
→
Set
setting mode 2 from No. 0 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the RETURN button (BS3) once.
(3) Press the SET button (BS2) one.
(4) Press the RETURN button (BS3) twice.
(5) Press the MODE button (BS1) once.
• To inhibit STD1 and STD2 compressors from
operating
→
Set setting mode 2 from No. 19 to No.
2. (REYQ8M to REYQ16M)
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
• To inhibit STD2 compressor from operating
→
Set
setting mode 2 from No. 19 to No.3.(REYQ14M)
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) twice.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
Caution
"For making a compressor unable to operate due to malfunction, etc., be sure to
conduct the work with emergency operation setting.
Never execute work such as disconnection of the power cable from magnet contactor.
(Otherwise, other normal compressors may malfunction.)
∗∗∗∗
Because the units will be operated in the combination with which oil pressure
equalization between compressors cannot be performed.
LED display (
7
:ON
7
7
:OFF
9
9
:Blink)
H1P---H7P
(Factory set)
7
777777
777777
777777
777779
9
77777
77779
97
7
7777777
777777
77
7777777
7777
LED display (
7
:ON
7
7
:OFF
9
9
:Blink)
H1P---H7P
(Factory set)
7
777777
777777
77
7777
7777
777777
777779
9
77777
77779
97
7
7777777
777777
77
7777777
7777
LED display (
7
:ON
7
7
:OFF
9
9
:Blink)
H1P---H7P
(Factory set)
7
777777
777777
77
7777
7777
777777
777779
9
77777
777799
99
7777777
777777
77
7777777
7777
Summary of Contents for VRV II REYQ10MY1B
Page 19: ...Model Selection Si39 306 8 General Information ...
Page 150: ...Si39 306 Troubleshooting by Remote Controller Troubleshooting 139 ...
Page 250: ...Si39 306 Piping Diagrams Appendix 239 REYQ14MY1B REYQ16MY1B 4D042070A ...
Page 252: ...Si39 306 Piping Diagrams Appendix 241 1 3 BS Unit BSVQ100MV1 BSVQ160MV1 BSVQ250MV1 4D042115 ...
Page 254: ...Si39 306 Wiring Diagrams for Reference Appendix 243 REYQ14MY1B REYQ16MY1B 3D038572 ...
Page 256: ...Si39 306 Wiring Diagrams for Reference Appendix 245 REYQ18 20 22 24 26 28 30 32MY1B 3D043436 ...
Page 257: ...Wiring Diagrams for Reference Si39 306 246 Appendix REYQ34 36 38 40 42 44 46 48MY1B 3D043437 ...
Page 259: ...Wiring Diagrams for Reference Si39 306 248 Appendix FXCQ40M 50M 80M 125MVE 3D039557A ...
Page 260: ...Si39 306 Wiring Diagrams for Reference Appendix 249 FXZQ20M 25M 32M 40M 50MVE 3D038359 ...
Page 262: ...Si39 306 Wiring Diagrams for Reference Appendix 251 FXKQ25M 32M 40M 63MVE 3D039564A ...
Page 264: ...Si39 306 Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A ...
Page 265: ...Wiring Diagrams for Reference Si39 306 254 Appendix FXMQ200M 250MVE 3D039621A ...
Page 266: ...Si39 306 Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C ...
Page 267: ...Wiring Diagrams for Reference Si39 306 256 Appendix FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A ...
Page 283: ...REFNET Pipe System Si39 306 272 Appendix ...
Page 284: ...Si39 306 Appendix 273 DPSOH RI RQQHFWLRQ 5 7 SH 5 4 0 HDW 5HFRYHU ...
Page 285: ...Si39 306 274 Appendix ...
Page 291: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 306 280 Appendix ...
Page 305: ...Si39 306 iv Index ...