FXCQ20~125M7V1B
VRV System air conditioners
4PW15108-1

Installation and operation manual

3

4.

Adjust the unit to the right position for installation.

(Refer to the chapter "

Preparations before installation

")

5.

Check if the unit is horizontally levelled.

Do not install the unit tilted. The indoor unit is equipped with a
built-in drain pump and float switch.
(If the unit is tilted against condensate flow, the float switch may
malfunction and cause water to drip.)

Check if the unit is levelled at all four corners with a water level or
a water-filled vinyl tube as shown in 

figure 7

.

6.

Remove the paper pattern for installation (For new ceilings only.)

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.
Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for R-410A.

Apply ether oil or ester oil around the flare portions before
connecting.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Do not mix anything other than the specified refrigerant, such as
air, etc.., inside the refrigerant circuit.

Refer to Table 1 for the dimensions of flare nut spaces and the
appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)

When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand 3 or
4 turns before tightening firmly. 

Check the pipe connector for gas leaks.

If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a
fire.

Finally make sure there is no refrigerant gas leak. A toxic gas
may be released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.

Table 1

D

RAIN

 

PIPING

 

WORK

Rig the drain piping as shown in figure and take measures against
condensation. Improperly rigged piping could lead to leaks and
eventually wet furniture and belongings.

1.

Install the drain pipes.

Keep piping as short as possible and slope it downwards so that
air may not remain trapped inside the pipe. 

Keep pipe size equal to or greater than that of the connecting
pipe (Vinyl pipe of 25 mm nominal diameter and 32 mm outer
diameter).

Insert the supplied drain hose into the drain socket, up to the
white tape.

Tighten the clamp until the screw head is less then 4 mm from
the hose. 

Insulate the drain hose inside the building.

If the drain hose cannot be sufficiently set on a slope, fit the hose
with drain raising piping (field supply). 

How to perform piping 

(See figure 8)

1

Connect the drain hose to the drain raising pipes, and insulate
them.

2

Connect the drain hose to the drain outlet on the indoor unit, and
tighten it with the clamp.

1

Water level

2

Vinyl tube

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Coat here with ether oil or 
ester oil

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting of liquid line 
(supplied with the unit) 

4

Insulation for fitting of gas line 
(supplied with the unit) 

5

Clamps
(use 2 clamps per insulation)

2

3

1

4

5

3

2

1

4

Pipe gauge

Tightening torque

Flare dimension A 

(mm)

Flare shape

Ø6.4

14.2~17.2 N•m

(144~176 kgf•cm)

8.7~9.1

Ø9.5

32.7~39.9 N•m

(333~407 kgf•cm)

12.8~13.2

Ø12.7

49.5~60.3 N•m

(504~616 kgf•cm)

16.2~16.6

Ø15.9

61.8~75.4 N•m

(630~770 kgf•cm)

19.3~19.7

1

Hanging bar

1

Clamp metal 

2

Drain hose

3

White tape (field supply)

1

Ceiling slab

2

Hanger bracket

3

Adjustable (310 or less)

4

Drain raising pipe

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

R0.4~0.8

45

° ±

2

90

°±

0.5

A

1-1.5 m

1

2

1

3

Summary of Contents for VRV FXCQ20M7V1B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXCQ20M7V1B FXCQ25M7V1B FXCQ32M7V1B FXCQ40M7V1B FXCQ50M7V1B FXCQ63M7V1B FXCQ80M7V1B FXCQ125M7V1B System air conditioner...

Page 2: ...20 20 C B 2 6 A 7 5 D 1 2 3 4 12 12 1 2 3 4 11 11 5 6 8 7 9 13 12 10 11 3 4 2 1 13 13 P 1 P 2 F 1 F 2 T 1 T 2 8 7 5 6 4 3 1 2 8 8 300 mm 1 15 m 600 290 2 3 4 6 5 1 9 9 100 mm 1 10 10 1 7 5 6 2 3 4 5...

Page 3: ...P2 F1 F2 T1 T2 1 2 3 4 19 19 S M S S M 2 3 1 21 21 SETTING 2 1 4 3 16 16 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1...

Page 4: ...vande dokument under f ruts ttning att anv ndning sker i verensst mmelse med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standard er eller andre normgivende dokument er und...

Page 5: ...request and install in an appropriate place Refer to catalogues and technical literature for selecting a suitable remote controller Decoration panel For the following items take special care during c...

Page 6: ...8 or M10 size bolt Use anchors for existing ceilings and a sunken insert sunken anchors or other field supplied parts for new ceilings to reinforce the ceiling in order to bear the weight of the unit...

Page 7: ...igerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Table 1 DRAIN PIPING WORK Rig the drain piping as s...

Page 8: ...on manual of the remote controller All wiring must be performed by an authorized electrician A circuit breaker capable of shutting down power supply to the entire system must be installed This system...

Page 9: ...to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do not obstruct other equipment such as popping open the service cover Make...

Page 10: ...ON OF THE DECORATION PANEL Refer to the installation manual attached to the decoration panel After installing the decoration panel ensure that there is no space between the unit body and decoration pa...

Page 11: ...filters arrow direction facing upward push up along the guide Replace the air filter by performing the filter removal procedure in reverse 5 Shut the air inlet grill Refer to item No 1 6 After turning...

Page 12: ...N OFF BUTTON H1P LIGHT EMITTING DIODE ON RED H2P LIGHT EMITTING DIODE TIMER GREEN H3P LIGHT EMITTING DIODE FILTER SIGN RED H4P LIGHT EMITTING DIODE DEFROST ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELE...

Page 13: ...NOTES NOTES...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN15108 1...

Reviews: