Troubleshooting by Error Code
SiUS342303E
319
Part 6 Service Diagnosis
3.46 Outdoor Fan PCB Abnormality
Applicable
Models
All outdoor unit models
Error Code
H7
Method of Error
Detection
Detect with current sensor value.
Error Decision
Conditions
When the current sensor shows abnormality.
Supposed
Causes
Defective fan PCB
Troubleshooting
Properly connect the connector.
NO
YES
Replace the relevant fan motor.
(M1F, M2F)
NO
YES
Check for fan PCB applicable to the error code
H7
while in
monitor mode.
H7-21/23: Fan PCB (M1F) Master / Sub
H7-22/24: Fan PCB (M2F) Master / Sub
Replace the fan PCB.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the
connector of relevant
fan motor normally
connected?
Resistance
between U, V, W
phases of the fan motor
power supply cable has lost
balance or short circuit is
caused between U,
V, W phases.
Turn OFF the power supply
and wait for 10 minutes.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...