Troubleshooting by Error Code
SiUS372201EB
383
Part 6 Service Diagnosis
3.45 Discharge Pipe Temperature Abnormality
Applicable
Models
All outdoor unit models
Error Code
F3
Method of Error
Detection
Detect according to temperature detected with the discharge pipe or compressor body thermistor.
Error Decision
Conditions
When discharge pipe temperature becomes abnormally high (i.e., 135°C (275°F) or more)
When discharge pipe temperature sharply rises (remains at 120°C (248°F) or more for a period
of consecutive 10 minutes)
When compressor surface temperature becomes abnormally high (i.e., 120°C (248°F) or more)
When compressor surface temperature sharply rises (remains at 115°C (239°F) or more for a
period of consecutive 10 minutes)
Supposed
Causes
Abnormal discharge pipe temperature
Defective discharge pipe thermistor
Abnormal compressor surface temperature
Defective compressor body thermistor
Defective outdoor unit main PCB
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...