Troubleshooting by Error Code
SiUS372201EB
299
Part 6 Service Diagnosis
3.2 Error Codes (Sub Codes)
If an error code like the one shown below is displayed when a wired remote controller is in use,
make a detailed diagnosis or a diagnosis of the relevant unit.
3.2.1 Indoor Unit
Error code
Troubleshooting
Error Description
Diagnosis
A0 - 01
External protection device abnormality
Refer to page 314.
A6 - 01
Fan motor locked
A locked fan motor current has been detected. Turn the fan
by hand to check for the connection of connectors.
A6 - 10
Fan overcurrent error
A fan motor overcurrent has been detected. Check for the
connection of the connector between the fan motor and the
fan PCB. If the connection is normal, replace the fan motor.
If this still cannot solve the error, replace the fan PCB.
A6 - 11
Fan position detection error
An error in the detection of position of the fan motor. Check
for the connection of the connector between the fan motor
and the fan PCB. If the connection is normal, replace the
fan motor. If this still cannot solve the error, replace the fan
PCB.
A6 - 20
Indoor fan motor status abnormality
Refer to page 328.
A6 - 21
Low indoor airflow
Refer to page 329.
A8 - 01
Power supply voltage error
Check for the input voltage of the fan motor.
A9 - 01
Electronic expansion valve error
There is an error in the electronic expansion valve coil or a
connector disconnected.
A9 - 02
Refrigerant leakage detection error
Refrigerant leaks even if the electronic expansion valve is
closed. Replace the electronic expansion valve.
AA - 03
Gas furnace abnormality
Refer to page 335.
AH - 03
Transmission error (between the self-cleaning decoration
panel and the indoor unit)
(when the self-cleaning decoration panel is mounted)
Check for the connection of the harness connector
between the panel PCB and the indoor unit PCB.
AH - 04
Dust detection sensor error
(when the self-cleaning decoration panel is mounted)
Check for the connections of the connector X12A on the
panel PCB and the connectors X18A and X19A on the
sensor PCB.
AH - 05
Dust collection sign error
(when the self-cleaning decoration panel is mounted)
Check for clogging with dust at the dust collection port as
well as in the brush unit, S-shaped pipe, and dust box.
Furthermore, check for any stains of the light receiving and
emitting parts of the infrared unit.
AH - 06
Air filter rotation error
(when the self-cleaning decoration panel is mounted)
Check for anything getting in the way of rotating the filter
(e.g. the filter comes off or the drive gear is clogged with
foreign matter).
AH - 07
Damper rotation error
(when the self-cleaning decoration panel is mounted)
The damper does not rotate normally. Check for any
foreign matter around the damper and for the operation of
the gear and limit switch.
AH - 08
Filter self-cleaning operation error
(when the self-cleaning decoration panel is mounted)
The unit has not yet completed the filter self-cleaning
operation even after the lapse of specified period of time.
Check for any external noise, etc.
AH - 09
Filter self-cleaning operation start disabled error
(when the self-cleaning decoration panel is mounted)
The unit has been put into a state in which the filter self-
cleaning operation is disabled. Check the unit for the
operating conditions.
AJ - 01
Capacity setting error
There is an error in the capacity setting of the indoor unit
PCB.
AJ - 02
Electronic expansion valve setting error
There is a fault in the setting of the gear type electronic
expansion valve/direct acting type electronic expansion
valve.
C1 - 01
Transmission abnormality between indoor unit
PCB and fan PCB
Check for the conditions of transmission between the
indoor unit PCB and the fan PCB.
C1 - 07
Blower motor communication error
Refer to page 351.
C1 - 08
Climate Talk Communication error
Refer to page 352.
C6 - 01
Defective combination of indoor unit PCB and the fan PCB A combination of indoor unit PCB and the fan PCB is
defective. Check whether the capacity setting adaptor is
correct and the type of the fan PCB is correct.
Blower motor HP mismatch
Refer to page 356.
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...