Troubleshooting by Error Code
SiUS372201EB
329
Part 6 Service Diagnosis
Reference
3.12 Low Indoor Airflow
Applicable
Models
FXTQ-TA, FXTQ-TB
Error Code
A6-21
Outline
Error is issued if the indoor unit determines that the indoor fan motor rotation is insufficient,
regardless of the rotation command from indoor unit.
Error Decision
Conditions
Determining successive abnormalities
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
If that figure exceeds 50 rpm and falls below 150 rpm 10 times successively, it is deemed
abnormal operation.
If, during operation, the rotation command is stopped, the 5-second interval check is halted and
the counted number will be cleared.
Determining long-term abnormalities
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
Performs rotation sampling 720 times (takes approximately one hour), and if the rotation speed
exceeds 50 rpm and falls below 150 rpm over 360 times, it is deemed abnormal operation.
When the counter reaches 720 times, the counted number will be cleared and the 720 times
sampling restarts.
If, during this, the rotation command is stopped, the 5-second interval check is halted, but the
counted number will be kept.
When the rotation command is restarted, the checks will resume.
Error Reset
Conditions
Determining successive abnormalities
Checks the rotation speed at 5-second intervals using the feedback of the fan motor. If that
figure exceeds 150 rpm even once, the error will be cleared.
Determining long-term abnormalities
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
If that figure exceeds 150 rpm 36 times successively, the error will be cleared.
At that point, the counted number and sampling number will be cleared, and the 720 times
sampling starts again from the beginning.
Supposed
Causes
Fan or motor obstruction
Blocked filters
Restrictive ductwork or ductwork undersized
Wiring disconnected
Wrong outdoor and indoor combination
Indoor fan motor failure
Corrective
Actions
Check for obstruction on the fan or motor.
Check ductwork and filter for blockage.
Clean filters.
Remove obstruction. Verify all registers are fully open.
Check the connections and the rotation of the motor.
Verify the input voltage at the motor.
Verify ductwork is appropriately sized for system. Resize or replace ductwork if needed.
Replace motor.
CHECK 19
Refer to page 474.
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...