Outline of Control (Indoor Unit)
Part 4 Functions and Control
202
Note(s)
9.15 Fan Control (Heater Residual) (FXTQ-TA, FXTQ-TB
Models)
Outline
If the indoor heater turned OFF from ON during heating operation, the fan will keep operating for
further period of time in order to cool the heater.
Detail
9.16 Interlocked with External Equipment (FXTQ-TA, FXTQ-TB,
CXTQ-TA Models)
9.16.1 Air Purifier (UV Lamp)
When an air purifier is connected onsite, the fan is operated with the airflow rate set of the remote
controller or with the H tap.
9.16.2 Humidifier
When a humidifier is connected onsite, the fan operates with the airflow rate set of the remote
controller or with the H tap.
This control is not applicable to the humidifier connected to the wiring adaptor, but to the humidifier
connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB.
1. When the heater is ON, the airflow rate of the fan will be whichever is the largest between
the CFM dictated by the heater's own capacity, or the fan tap CFM determined by other
controls.
2. Fan residual operation will continue, even if the indoor unit is turned off with the remote
controller operation button.
•
Heater turned OFF from ON
OR
•
Heater ON
•
Time up (
∗
2)
Residual OFF
Residual ON
Fan (
∗
1)
ENTRY/
90 sec. timer starts.
1. External input ON is an input signal to the X1M-AIR CLEANER terminal on the PCB.
&
Fan operation at preset tap
(Fan tap can be changed by field setting
14 (24)-4.)
•
Remote control operation
(including thermostat OFF)
•
External input: ON (
∗
1)
1. External input ON is an input signal to the X1M-HUMIDIFIER terminal on the PCB.
&
&
•
Remote control operation: ON
(including thermostat OFF)
•
When the external input
changes from ON to OFF.
•
Remote control operation: ON
(including thermostat OFF)
•
External input: ON (
∗
1)
Fan operation at preset tap
(Fan tap can be changed by field setting
14 (24)-4.)
Fan residual operation for 30 seconds
(Fan tap can be changed by field setting
14 (24)-4.)
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...