20
|
Electrical installation
Installer and user reference guide
135
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
a
Wiring between the units (indoor-outdoor) (F1/F2 left)
b
Internal interconnection wiring (Q1/Q2)
c
Plastic bracket
d
Tie wrap (field supply)
e
P-clamp for cable shield earthing
Fix to the indicated plastic brackets using field supplied clamping material.
The indoor F1/F2 interconnection wiring MUST be shielded wire. The shielding is
earthed via a metal P-clamp (e) (only at outdoor unit). Strip the insulation up to the
shielding mesh, to provide full contact of the earth with the shielding.
20.3 To connect the interconnection wiring
The wiring from the indoor units must be connected to the F1/F2 (In‑Out)
terminals on the PCB in the outdoor unit.
See
"20.1.6 Specifications of standard wiring components"
132] for wiring
requirements.
INDOOR
UNIT
A
INDOOR
UNIT
B
INDOOR
UNIT
C
INDOOR
UNIT
D
OUT-
DOOR
UNIT
SV
UNIT
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 F1 F2
TO
IN/D
TO
OUT/D
F1 F2 F1 F2
TO
MULTI
UNIT
Q1 Q2
c
d
TO
IN/D
TO
OUT/D
F1 F2 F1 F2 Q1 Q2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
TO
MULTI
UNIT
TO
IN/D
TO
OUT/D
F1 F2 F1 F2 Q1 Q2
TO
MULTI
UNIT
b
1
a
1
a
2
a
3
OUT-
DOOR
UNIT
SV
UNIT
F1 F2 F1 F2
b
2
a1
Unit A (master outdoor unit)
a2
Unit B (slave outdoor unit)
a3
Unit C (master outdoor unit with direct connection to indoor units)
b1
SV unit 1
b2
SV unit 2
c
Indoor unit
d
Outdoor unit/other system interconnection (F1/F2)
▪
The interconnecting wiring between the outdoor units in the same piping system
must be connected to the Q1/Q2 (Out Multi) terminals. Connecting the wires to
the F1/F2 terminals results in system malfunction.
▪
The wiring for the other systems must be connected to the F1/F2 (Out-Out)
terminals of the PCB in the outdoor unit to which the interconnecting wiring for
the indoor units is connected.
▪
The base unit is the outdoor unit to which the interconnecting wiring for the
indoor units is connected.
Tightening torque for the interconnection wiring terminal screws:
Screw size
Tightening torque [N•m]
M3.5 (A1P)
0.8~0.96