12.2

Precautions when troubleshooting

WARNING

▪ When  carrying  out  an  inspection  on  the  switch  box  of

the  unit,  ALWAYS  make  sure  that  the  unit  is
disconnected  from  the  mains.  Turn  off  the  respective
circuit breaker.

▪ When a safety device was activated, stop the unit and

find  out  why  the  safety  device  was  activated  before
resetting  it.  NEVER  bridge  safety  devices  or  change
their  values  to  a  value  other  than  the  factory  default
setting.  If  you  are  unable  to  find  the  cause  of  the
problem, call your dealer.

DANGER: RISK OF ELECTROCUTION

WARNING

Prevent hazards due to inadvertent resetting of the thermal
cut-out: this appliance MUST NOT be supplied through an
external switching device, such as a timer, or connected to
a circuit that is regularly turned ON and OFF by the utility.

12.3

Solving problems based on error
codes

In  case  of  a  displayed  malfunction  code,  consult  the  dealer  where
the unit was purchased.

12.3.1

Error codes: Overview

Malfunction code

Particular code

Description

EEPROM failure

Locked rotor

22

Unstable fan rpm: failure of filter contamination check or failure of function 19(29)-0-04/-05

Power supply malfunction

Capacity setting malfunction

Fan communication error

Malfunction of fan motor sensor or fan control driver

CO

2

 sensor warning

Transmission error between the unit and user interface

Transmission error between main user interface and sub user interface

Wrong user interface installed

Repeated central address

Transmission error between the unit and centralised controller

External protection device activated

01

Indoor air thermistor (R1T) malfunction

02

Indoor air thermistor (R1T) out of operation range

01

Outdoor air thermistor (R2T) malfunction

02

Outdoor air thermistor (R2T) out of operation range

03

Functions 19(29)-0-04/-05 not possible due to low outdoor temperature operation

Damper-related malfunction

Damper-related malfthermistor

In case of malfunction with the code on grey background, the unit still operates. However, make sure to have it inspected and repaired as soon as
possible.

13

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  the
dismantling  of  the  system  MUST  comply  with  applicable
legislation.  Units  MUST  be  treated  at  a  specialised
treatment facility for reuse, recycling and recovery.

14

Technical data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

extranet (authentication required).

14.1

Wiring diagram: Heat reclaim
ventilation unit

The wiring diagram is delivered with the unit, located on the outside
of the service cover.

Legend for wiring diagrams:

A1P

Printed circuit board

A2P~A5P

Printed circuit board assy (fan)

C7

Capacitor (M1F)

F1U

Fuse (250 V, 6.3 A, T) (A1P)

HAP

Pilot lamp (service monitor - green)

K1R

Magnetic relay (A1P)

K2R

Magnetic relay (A1P)

L1R~L4R

Reactor

M1D

Motor (damper)

PS

Switching power supply

Summary of Contents for VAM350J7VEB

Page 1: ...reference guide Heat reclaim ventilation unit English Nam e Plat e Installer and user reference guide Heat reclaim ventilation unit VAM350J7VEB VAM500J7VEB VAM650J7VEB VAM800J7VEB VAM1000J7VEB VAM1500...

Page 2: ...control systems 20 7 2 Independent system 21 7 3 Interlocked system 21 7 4 Centralised control system 22 8 Configuration 22 8 1 Operating procedure 22 8 1 1 To change the settings with BRC1E53 22 8 1...

Page 3: ...nce shall NOT be made by children without supervision WARNING To prevent electric shocks or fire Do NOT rinse the unit Do NOT operate the unit with wet hands Do NOT place any objects containing water...

Page 4: ...age of flammable gases example thinner or gasoline carbon fibre ignitable dust In places where corrosive gas example sulphurous acid gas is produced Corrosion of copper pipes or soldered parts may cau...

Page 5: ...of your application for more information NOTICE Make sure water quality complies with EU directive 98 83 EC 1 3 6 Electrical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the...

Page 6: ...ns Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Format Paper in the a...

Page 7: ...and user reference guide 7 VAM350 2000J7VEB Heat reclaim ventilation unit 4P487293 1 2017 08 3 2 Heat reclaim ventilation unit 3 2 1 To unpack the heat reclaim ventilation unit VAM350 VAM500 VAM650 1...

Page 8: ...3 To handle the heat reclaim ventilation unit NOTICE When removing the heat reclaim ventilation unit from the packing do NOT place the suction or discharge side of the unit on the floor Possible conse...

Page 9: ...the outdoor air When the heat reclaim ventilation unit is installed upside down the minimum allowed outdoor air temperature is 5 C If this CANNOT be guaranteed you MUST install a heater to heat up th...

Page 10: ...temperature or direct flames Places subject to much carbon black Carbon black attaches to air filter and heat exchange elements disabling them 5 2 1 Installation site requirements for the heat reclaim...

Page 11: ...plied with the fixing box 1 Remove the screws that are in the middle of the casing fixing plate 2 Attach the optional mounting plate EKMPVAM on top of the casing fixing plate 3 Attach the optional ada...

Page 12: ...Field supplied fuses 16 A Wire H05VV U3G Size Wire size MUST comply with the applicable legislation Transmission wiring Wiring Shielded wire 2 wire Size 0 75 1 25 mm Precautions When connecting more t...

Page 13: ...n the return air infiltrates into the ceiling and the temperature and humidity in the ceiling become too high insulate the metal parts of the unit ONLY use the service hole to access the inside of the...

Page 14: ...ll a heater to heat up the outdoor air to 5 C Keep in mind that the ceiling hooks have to be reinstalled when the heat reclaim ventilation unit is installed upside down They have to be rotated 180 so...

Page 15: ...he General safety precautions chapter WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation Make electrical connections to the fixed wiring...

Page 16: ...nected to the main units Remove the screw that secures the cover and open the switch box Secure the power supply control wires with the clamp as shown in the figures VAM350 650 X33A a X14A J3 J2 J1JC...

Page 17: ...r e Grounding terminal f Terminal board g Transmission wiring terminal board P1 P2 F1 F2 h Transmission wiring to optional user interface i Power supply cable j Wires for connection of additional exte...

Page 18: ...4P487293 1 2017 08 VAM1500 VAM2000 a g p b m b b b f k i m l j r n h m d e o A1P X24A X29A X27A X35A X14A X33A F2 F1 P2P1 J3J2 J1JC a b f k d e m l i j r n h o o m X35A X24A c i o r n h l q q q c a Sw...

Page 19: ...entilation fan starts operating and it will open the contact when the fan is stopped 6 5 4 Power supply connection control wire terminals and switches on the circuit board To connect the power supply...

Page 20: ...mode fresh up mode Malfunction display Interlocked operation control system Interlocked operation with indoor unit by user interface for indoor unit Maximum 16 units The heat reclaim ventilation unit...

Page 21: ...0 m See 8 3 2 Independent system on page 29 Heat reclaim ventilation unit User interface 7 3 Interlocked system System Standard method Related items in electric wiring Combined operation system with V...

Page 22: ...ts divided by Mode number for example 19 29 where 19 is the mode number for group settings and 29 is the mode number for individual settings Switch number for example 1 Position number for example 02...

Page 23: ...s to enter the local setting mode 2 Use the Ventilation mode button up b and the Airflow rate button down b to select a mode number Result The code display is blinking 3 To configure settings for indi...

Page 24: ...er 8 hours 2 Pre cool pre heat Off On 3 Pre cool pre heat duration 30 minutes 45 minutes 60 minutes 4 Initial fan speed High Ultra high 5 Yes No setting for duct connection with VRV system Without duc...

Page 25: ...tion 4 Indication of ventilation mode On Off 18 28 6 Automatic ventilation air flow mode Linear Fixed A Fixed B 7 Fresh up mode No indication supply No indication exhaust Indication supply Indication...

Page 26: ...Step 6 Step 7 Step 8 2 Supply fan step setting Step1 Step2 Step3 Step4 Step5 Step6 Step7 Step8 Step 9 Step 10 Step 11 Step 12 Step 13 Step 14 Step 15 3 Exhaust fan step setting Step1 Step2 Step3 Step4...

Page 27: ...ing modes are mentioned as group settings Between parentheses are the setting modes for individual unit control Group number setting for centralised controller Mode No 00 Group controller Mode No 30 I...

Page 28: ...ng 19 29 2 and setting 19 29 3 Balance return air and outdoor air with fan steps 1 15 based on the air flow curves see the databook and the system pressure drop You MUST activate setting 19 29 0 03 Wa...

Page 29: ...ter d Switch position Slave e Maximum length of connection line 500 m NOTICE Factory settings Do NOT change the switch settings when a user interface is connected SS1 is a setting switch to operate wi...

Page 30: ...hout user interface do NOT switch it on with the user interface connected Otherwise the unit will give an error once the controller is removed because it will keep on searching for the user interface...

Page 31: ...to set the central control group number Mode number 00 Central control group number 2 05 Zone control F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 P1 P2 P1 P2 P1 P2 P1 P2 HRV 1 HRV 2 HRV 3 VRV a b e c d c a Zone 1...

Page 32: ...ilation units are operating 1 Press the Operation Mode Selector button several times until the ventilation mode is selected Vent To change the ventilation mode 1 Press the Menu Enter button to display...

Page 33: ...terface BRC301B61 In such cases use the air conditioner user interface BRC1E53 or the centralised controller TEST FRESH UP 1 2 8 4 3 9 10 13 12 11 6 1 Operation lamp This red pilot lamp lights up whil...

Page 34: ...it board BRP4A50A to monitor the operation 1 Connect the terminal strip on the adapter printed circuit board BRP4A50A a b c d BRP4A50A X1 X2 L N X33A a Operation lamp b Power source c Power source d H...

Page 35: ...y Exhaust Weak High Low Low High Strong Ultra high High High Ultra high 8 5 3 About the external damper operation Functions Intake of outdoor air when the heat reclaim ventilation unit is off can be p...

Page 36: ...nstallation manual that is delivered with the CO2 sensor To remove the components a b c d d d d c e PS f g a Hinge mechanism b Service cover c Heat exchange element d Air filter e Heat exchange elemen...

Page 37: ...onditions The indoor temperature is higher than the air conditioning setting The outdoor temperature is lower than the indoor temperature If the above conditions are NOT met reevaluation takes place e...

Page 38: ...e performing a test operation is dangerous CAUTION Do NOT insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury 9 3 Checklist be...

Page 39: ...of electrostatic discharge Before performing any maintenance or service work touch a metal part of the unit in order to eliminate static electricity and to protect the PCB 11 2 1 To prevent electrical...

Page 40: ...nit and user interface Transmission error between main user interface and sub user interface Wrong user interface installed Repeated central address Transmission error between the unit and centralised...

Page 41: ...als Connectors Protective earth Noiseless earth Colours BLK Black BLU Blue BRN Brown GRN Green ORG Orange RED Red WHT White YLW Yellow For the user 15 User interface CAUTION NEVER touch the internal p...

Page 42: ...fore accessing make sure to turn off the operation switch and disconnect the power CAUTION During operation NEVER check or clean the unit It may cause electrical shock Do NOT touch the rotating parts...

Page 43: ...or centralised controller Refer to 8 Configuration on page 22 Check if the indication of operation standby on the user interface is shown It indicates the pre cooling pre heating operation This unit...

Page 44: ...ng how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...4P487293 1 2017 08 Copyright 2017 Daikin...

Reviews: