11 Unit installation
Installation and operation manual
11
VAM350~2000J8VEB
Heat reclaim ventilation unit
4P664011-1 – 2021.08
4
Follow the installation instructions provided with the option kits
(BRP4A50A, KRP2A51 and KRP1BA101).
5
Guide the PCB wire through the dedicated holes and attach it
as instructed in "Opening the switch box" in the installer and
user reference guide.
6
Attach the options to the optional mounting plate, as shown in
the figure.
7
After the wires are connected, fasten the switch box cover.
For models 1500+2000
a
e
f
f
f
g
b
b + c
c
a
BRP4A50A (optional accessory)
b
KRP2A51 (optional accessory)
c
KRP1BA101 (installation box)
d
EKMP65VAM (mounting plate)
f
Screw
g
Screw (supplied with the installation box)
1
Remove the screws from the middle of the plate connecting the
2 units.
2
Attach the optional mounting plate (EKMPVAM) on top of the
plate connecting the 2 units.
3
Attach the optional adapter PCB (KRP2A51) in the installation
box (KRP1BA101).
4
Follow the installation instructions provided with the option kits
(BRP4A50A, KRP2A51 and KRP1BA101).
5
Guide the PCB wire through the dedicated holes and attach it
as instructed in "Opening the switch box" in the installer and
user reference guide.
6
Attach the options to the optional mounting plate, as shown in
the figure.
7
After the wires are connected, fasten the switch box cover.
11.2.2
To install the duct flanges
1
Position the duct flanges (a) over the duct holes.
2
Secure the duct flanges with the provided screws (b) (see
accessory bag).
a
b
a
Duct flange
b
Screw
Model
Required screws
Duct flanges
VAM350
16
4× Ø200 mm
VAM500
16
4× Ø200 mm
VAM650
24
4× Ø250 mm
VAM800
24
4× Ø250 mm
VAM1000
24
4× Ø250 mm
VAM1500
48
8× Ø250 mm
VAM2000
48
8× Ø250 mm
11.2.3
To install the EKVDX option
See
For more information, see the Installation and operation manual of
the EKVDX.
11.3
Unit orientation
The following illustration helps you to install the heat reclaim
ventilation unit in the correct position:
Normal installation
Upside down installation