Si71-502
Troubleshooting
Troubleshooting
53
1.18
Power Transformer
Error Detection
Method
Check resistance and voltage with tester, and insulation resistance with megger.
Error Generating
Conditions
Possible Causes
Troubleshooting
Resistance of primary side of transformer: approx. 140
Ω
Resistance of secondary side of transformer: approx. 1.9
Ω
Voltage at secondary side of transformer when rated voltage is applied to primary side: approx. 26 VAC
Insulation resistance between primary side of transformer and case: 100 M
Ω
or higher
Insulation resistance between secondary side of transformer and case: 100 M
Ω
or higher
Insulation resistance between primary side and secondary side of transformer: 100 M
Ω
or higher
Check resistance of
primary side of
transformer.
Does
measured
resistance
deviate significantly
from values
shown
below?
YES
NO
Check resistance of
secondary side of
transformer.
Does
measured
resistance
deviate significantly
from values
shown
below?
YES
NO
Apply rated voltage to
primary side of
transformer, and check
output voltage of
secondary side
of transformer.
Does
measured
voltage deviate
significantly from
values shown
below?
YES
NO
Transformer is faulty.
Transformer is faulty.
Transformer is faulty.
Transformer is normal
(HF016)
(HL037)
Check resistance and voltage
Summary of Contents for VAM 150GJVE
Page 7: ...Introduction Si71 502 vi 1 1 1 Cautions in Operation and Maintenance ...
Page 8: ...Si71 502 Introduction vii ...
Page 13: ...General Constructions Si71 502 4 General Constructions ...
Page 29: ...Maintenance Si71 502 20 Maintenance ...
Page 43: ...Circuit Operations Si71 502 34 Circuit Operations ...
Page 103: ...After sales Service Si71 502 94 Operation Manual ...
Page 106: ...Si71 502 Appendix Appendix 97 VAM1500GJVE VAM2000GJVE ...
Page 107: ...Appendix Si71 502 98 Appendix ...