SiE71-202
Troubleshooting
Troubleshooting
45
1.12
Field Setting Error
Remote Controller
LCD Display
Error Code
UA
Inspection
5
Unit No.
1
LED Indication
Remote Controller
1
Main Unit
5
Error Detection
Method
Error Generating
Conditions
Possible Causes
Faulty combination of remote controller
More than 16 units connected to remote controller cable.
Faulty remote controller
Troubleshooting
<Combination-Right or Wrong>
Main body
Remote controller
Right/Wrong
Heat recovery ventilation unit only
Heat recovery ventilation unit
Right
Heat recovery ventilation unit only
Heat recovery ventilation unit + air-conditioner Wrong
Heat recovery ventilation unit only
Air conditioner
Right
Heat recovery ventilation unit + air-conditioner Heat recovery ventilation unit
Wrong
Heat recovery ventilation unit + air-conditioner Heat recovery ventilation unit + air-conditioner Right
Heat recovery ventilation unit + air-conditioner Air-conditioner
Right
YES
YES
Check the system, and correct
connections.
Change connections so that 16
or fewer units are connected to
remote controller cable.
Replace remote controller.
Is
combination
of remote
controller and heat
recovery ventilation
unit (air
conditioner)
correct?
NO
(HF011)
Are
17 or more
units connected
to remote
controller
cable?
NO
Refer "Combination-Right or Wrong"
Summary of Contents for VAM 1000FAVE
Page 5: ...SiE71 202 iv Table of Contents ...
Page 13: ...General Constructions SiE71 202 4 General Constructions ...
Page 37: ...Control Functions SiE71 202 28 Control Functions ...
Page 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Page 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Page 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Page 77: ...Appendix SiE71 202 68 Appendix ...
Page 81: ...SiE71 202 iv Index ...