Troubleshooting
Si-93
44
Troubleshooting
1.14
Main Unit PCB Assembly
Error Detection
Method
Check microcomputer operation monitor.
Error Generating
Conditions
When main unit PCB assembly does not operate.
When communication circuit errors.
Possible Causes
Fuse (excess current)
Power transformer
Noise
Main unit PCB
Troubleshooting
Main unit PCB
NO
NO
NO
YES
Does equipment
reset properly.
Is it flashing?
After checking
other possible
causes, replace
PCB assembly.
Is monitor indicator
Off?
YES
YES
Monitor indicator remains
On.
With remote controller
disconnected, check
microcomputer operation
monitor.
Turn off power, then
restart.
Noise may be causing erroneous
operation. If power reset does not
solve the problem, replace main unit
PCB.
There may be a malfunction in main
unit PCB fuse, main unit PCB or power
transformer.
Check fuse and transformer. If they are
normal, replace PCB.
Replace main unit PCB.
(HF013)
(HL033)
Fuse
Microcomputer operation
monitor (green LED)
FUSE
Summary of Contents for VAM 1000EJ
Page 5: ...Si 93 iv Table of Contents ...
Page 7: ...Introduction Si 93 vi 1 1 1 Cautions in Repair Warning ...
Page 8: ...Si 93 Introduction vii ...
Page 11: ...Si 93 2 General Constructions ...
Page 15: ...Si 93 6 Operation ...
Page 21: ...Si 93 12 Maintenance ...
Page 27: ...Si 93 18 Control Functions ...
Page 35: ...Si 93 26 Circuit Operations ...
Page 39: ...Si 93 30 Troubleshooting ...
Page 59: ...Troubleshooting Si 93 50 Troubleshooting ...
Page 61: ...Si 93 52 Supplementary Explanation ...
Page 72: ...Si 93 Appendix 63 Part 8 Appendix 1 Appendix 65 1 1 Wiring Diagram 65 ...
Page 73: ...Si 93 64 Appendix ...
Page 74: ...Si 93 Appendix Appendix 65 1 Appendix 1 1 Wiring Diagram VAM500EJVE VAM800EJVE VAM1000EJVE ...
Page 75: ...Appendix Si 93 66 Appendix VAM2000EJVE ...
Page 79: ...Si 93 iv Index ...