Si-93
Troubleshooting
Troubleshooting
39
1.9
Data Transmission Error (Between LCD Remote Controller and Main Unit)
Remote Controller
LCD Display
Error Code
UUU
U5555
Inspection
5
Unit No.
5
LED Indication
Remote Controller
5
Main Unit
5
Error Detection
Method
Microcomputer checks if data is transmitted properly between main unit and remote controller.
Error Generating
Conditions
When data transmission is not performed correctly for a certain time period.
Possible Causes
■
Faulty connection of remote controller cable
■
Faulty remote controller cable
■
External factor (noise, etc.)
Troubleshooting
Note:
Note 1:
1. Use tester to check continuity of remote controller cable.
■
Disconnect cable from main unit terminal board and remote controller terminal board. Measure
resistance between wires in cable. Resistance should be
∞
M
Ω
(infinity).
2. Use tester to check voltage at terminal board.
Check with power turned on.
■
With remote controller cable disconnected, voltage between P1 and P2 on terminal board should be
approx. 16 VDC. If measured value is not approx. 16 VDC, PCB assembly is faulty.
■
Connect remote controller cable and disconnect remote controller. Voltage at the end of remote
controller cable should be approx. 16 VDC. If measured value is not 16 VDC, remote controller cable is
faulty.
■
Connect remote controller cable and remote controller. Voltage between P1 and P2 on remote
controller terminal should be approx. 16 VDC. If measured valued is not 16 VDC, remote controller is
faulty.
Check connection of
remote controller cable to
control PCB assembly on
terminal board.
Is
remote
controller cable
normal?
Note 1
YES
YES
Correct wiring.
Replace remote controller
cable.
Possibility of external factor
(instead of equipment error).
Is
connection
cable between
main unit and remote
controller
properly
wired?
NO
(HF008)
NO
JC J2 J1 F2 F1
P2 P1
P2
P1
Main unit PCB
(HL032)
LCD remote
controller
Remote
controller
for heat
reclaim
ventilation unit
Summary of Contents for VAM 1000EJ
Page 5: ...Si 93 iv Table of Contents ...
Page 7: ...Introduction Si 93 vi 1 1 1 Cautions in Repair Warning ...
Page 8: ...Si 93 Introduction vii ...
Page 11: ...Si 93 2 General Constructions ...
Page 15: ...Si 93 6 Operation ...
Page 21: ...Si 93 12 Maintenance ...
Page 27: ...Si 93 18 Control Functions ...
Page 35: ...Si 93 26 Circuit Operations ...
Page 39: ...Si 93 30 Troubleshooting ...
Page 59: ...Troubleshooting Si 93 50 Troubleshooting ...
Page 61: ...Si 93 52 Supplementary Explanation ...
Page 72: ...Si 93 Appendix 63 Part 8 Appendix 1 Appendix 65 1 1 Wiring Diagram 65 ...
Page 73: ...Si 93 64 Appendix ...
Page 74: ...Si 93 Appendix Appendix 65 1 Appendix 1 1 Wiring Diagram VAM500EJVE VAM800EJVE VAM1000EJVE ...
Page 75: ...Appendix Si 93 66 Appendix VAM2000EJVE ...
Page 79: ...Si 93 iv Index ...