10
Heating capacity and heating power input performance table
UWL030B5
Using side LWT(ºC)
25
28
30
33
36
40
45
48
50
Cpapacity (kW)
Heat
source
EWT(ºC)
10
117.5
118.4
118.9
119.2
119.2
118.5
116.8
115.3
114.1
13
127
127.7
128
128.1
127.9
127
124.9
123.2
121.9
15
133.1
133.7
133.8
133.8
133.4
132.3
130.1
128.2
126.8
17
138.9
139.4
139.4
139.3
138.7
137.5
134.9
132.9
131.4
18
141.7
142.1
142.2
141.9
141.3
139.9
137.3
135.2
133.7
20
147.2
147.5
147.4
147
146.3
144.7
141.9
139.7
138
23
155.1
155.1
154.9
154.3
153.4
151.5
148.3
145.9
144
25
160
159.9
159.6
158.9
157.8
155.7
152.3
149.7
147.8
27
164.7
164.5
164.1
163.2
162
159.8
156.1
153.3
151.3
30
171.4
170.9
170.4
169.3
167.9
165.4
161.3
158.4
156.2
UWL030B5
Using side LWT(ºC)
25
28
30
33
36
40
45
48
50
Power (kW)
Heat
source
EWT(ºC)
10
16.3
18.2
19.4
21.3
23.2
25.8
28.9
30.8
32.1
13
16.6
18.4
19.7
21.5
23.4
25.9
28.9
30.8
32
15
16.8
18.6
19.9
21.7
23.5
25.9
29
30.8
32
17
17.1
18.9
20.1
21.8
23.6
26
29
30.8
32
18
17.2
19
20.2
21.9
23.7
26.1
29.1
30.8
32
20
17.5
19.2
20.4
22.1
23.9
26.2
29.1
30.9
32
23
17.9
19.6
20.7
22.4
24.1
26.4
29.2
30.9
32.1
25
18.2
19.8
20.9
22.6
24.3
26.5
29.3
31
32.1
27
18.5
20.1
21.2
22.8
24.5
26.7
29.4
31.1
32.2
30
18.9
20.5
21.6
23.2
24.8
26.9
29.6
31.2
32.3
Note: The parameters are tested base on unit rated water flow.