11
English
R407C is a zeotropic refrigerant mixture which has zero
ozone depletion potential and thus conformed to Montreal
Protocol regulation. It requires Polyester oil (POE) oil
for its compressor's lubricant. Its refrigerant capacity and
performance are about the same as the refrigerant R22.
POE or PVE oil is used as lubricant for R407C compressor,
which is different from the mineral oil used for R22
compressor. During installation or servicing, extra precaution
must be taken not to expose the R407C system too long
to moist air. Residual POE or PVE oil in the piping and
components can absorb moisture from the air.
Refrigerant R407C is more easily affected by dust of
moisture compared with R22, make sure to temporarily
cover the ends of the tubing prior to installation.
•
•
•
SERVICE OF THE FILTER
Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water (below 40°C) with a
neutral cleaning detergent.
Rinse the filter well and dry before placing it back onto the unit.
Do not use gasoline, volatile substances or chemicals to clean the filter.
Clean the filter at least once every 2 weeks. Or more frequently if neccesary.
Filter Position
The
fi
lters are mounted in front of the indoor heat exchanger.
* (Air
fi
lter : special order or
fi
eld supply)
•
•
•
•
UAT(Y)(P)60, 80, 100, 120, 150, 200A
UAT(Y)(P)250, 300, 360, 420A
Filter
Filter
Filter cover
Filter cover
Service panel
removed when servicing
note: both side for unit 150, 200A
removed when servicing
SPECIAL PRECAUTIONS WHEN DEALING WITH R407C UNIT
SERVICE AND MAINTENANCE
No additional charge of compressor oil is permitted.
No other refrigerant other than R407C.
Tools specifically for R407C only (must not be used for
R22 or other refrigerant)
Manifold gauge and charging hose
Gas leak detector
Refrigerant cylinder / charging cylinder
Vacuum pump c/w adaptor
Flare tools
Refrigerant recovery machine
Filter-dryer must be installed along the liquid line for
all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant
system. Filter-dryer must be of molecular sieve type. For
a heat-pump system, install a two-way flow filter-dryer
along the liquide line.
•
•
•
i)
ii)
iii)
iv)
v)
vi)
•