The unit is equipped with a refrigerant detection system that complies with Annex LL of the IEC 60335-2-40:2018,
which position has been checked according to test reported in Annex MM of IEC 60335-2-40:2018.
When the refrigerant detection system detects a leak, the following will be initiated by the unit:
• disable the compressor operation unless the compressors;
•
Supply and return (if present) fan control will be set to to constant airflow logic with a fix airflow value. The fans
will operate continuously even if time tables are set. This in order to not let the airflow to go below "Q
min
" (see
below);
• Energize a dedicated relay in the electrical cabinet in order to fully open any external zoning dampers;
•
Set the dampers (if installed on the appliance) in order to have a full intake of fresh air and a full expulsion of the
return air.
External zoning dampers, if present, must be connected to this relay in order to be open when a leak
is detected
Zoning dampers installed in rooms considered to determine the minimum room area must be
electrically powered at all times after installation, other than when servicing, to be effective for safety.
The refrigerant detection system and controls will maintain the above action until at least 5 min after the refrigerant
detection system has reset. Building fire and smoke systems may override this function.
If the leak detector detects a leak, the above operations will be initiated even if the unit is turned OFF
by button, by BMS or by digital input.
In addition to what above another dedicated relay is present in the unit electrical cabinet and
connected directly to the leak detector alarm. This relay can be used to monitor the leak detector
alarm even in case of a unit control board fault.
The minimum circulation airflow (Q
min
) circulated to the total conditioned space, expressed in m
3
⁄h, must be in
accordance with the following table:
Unit
For units without hot gas post heating coil
For units with hot gas post heating coil
m
c
Q
min
m
c
Q
min
[kg]
m
3
/h
[kg]
m
3
/h
UATYA25
7
-
1368
8,3
-
1613
UATYA30
10
-
1954
11,3
-
2208
UATYA40
12
-
2345
13,7
-
2680
UATYA50
15
-
2932
17
-
3326
UATYA60
18
-
3518
21
-
4095
UATYA70
18
-
3518
21
-
4095
UATYA80
23
-
4495
26,9
-
5255
UATYA90
24
-
4691
28
-
5479
UATYA100
28
-
5472
32,3
-
6315
UATYA110
30
-
5863
34,7
-
6783
UATYA120
36
-
7036
41,2
-
8059
UATYA140
19
19
3713
23,1
23,1
4515
UATYA150
19
19
3713
23,1
23,1
4515
UATYA160
23
23
4495
27,9
27,9
5453
UATYA180
25
25
4886
25
25
4886
UATYA190
25
25
4886
25
25
4886
Whenever the flow, measured by the differantial air presssure tranducer, falls below the values
reported in the table above, the airflow alarm from differential pressure transducer will be displayed on
the unit control and the unit will be stopped.
The supply and return air shall be directly ducted to the conditioned space. Open areas such as false ceilings shall
not be used as a return air duct.