STATIC BLOWER

CHILLED WATER FAN COIL UNIT

IM-SBBW-0308(4)-DAIKIN (ASEAN)

Part No.: R08019031563D

INSTALLATION MANUAL 

INSTALLATION MANUAL 

Summary of Contents for UAHMM20AV1

Page 1: ...STATIC BLOWER CHILLED WATER FAN COIL UNIT IM SBBW 0308 4 DAIKIN ASEAN Part No R08019031563D INSTALLATION MANUAL INSTALLATION MANUAL ...

Page 2: ......

Page 3: ...3 0 50 0 20 0 65 0 295 0 177 0 1402 0 1232 0 117 0 162 5 50 0 394 0 20 0 48 5 287 0 1462 0 1502 0 287 0 270 0 270 0 288 0 291 8 122 6 537 0 35 0 60 0 761 0 605 0 533 0 100 0 A 33 0 SEE DETAIL B 35 0 SEE DETAIL A A 122 6 437 0 572 0 33 0 122 6 SEE DETAIL B SEE DETAIL A 96 0 SEE DETAIL A 88 0 257 5 174 0 35 0 885 0 747 0 103 0 88 0 A SEE DETAIL B SEE DETAIL A SEE DETAIL B 1540 0 1370 0 53 0 50 0 20 ...

Page 4: ...y it may cause water leakage which will dampen the furniture Ensure that the unit s panel is closed after service or installation Unsecured panels will cause the unit to operate noisily Sharp edges and coil surfaces are potential locations which may cause injury hazards Avoid from being in contact with these places Before turning off the power supply set the remote controller s ON OFF switch to th...

Page 5: ...DED ROD RETURN FREE CEILING CHILLEDWATER SUPPLY Mounting Ensure that the overhead supports are strong enough to hold the unit s weight Position hanger rods and check for alignment with the unit Check that hangers are secure and that the base of fan coil unit is level in the two horizontal directions taking into account the gradient recommended for drainage flow as shown Check the gradient recommen...

Page 6: ...0 0 1000 0 800 0 UAHMM30AY1 UAHMM30AZY1 UAHMM40AY1 UAHMM40AZY1 Vertical Horizontal installation Vertical installation T T RETURN SUPPLY GAUGE COCK FAN COIL UNIT T T SUPPLY RISER RETURN RISER TEE JOINT 3 WAY MIXING VALVE FAN COIL UNIT Multiple fan coil unit installation T T FCU 1 FCU 2 FCU 3 GLOBE VALVE AIR VENT 3 WAY DIVERTING VALVE All three fan coil units to serve one area with a common thermost...

Page 7: ...unions is eliminated c Locate the control valve in between the gate valve and the equipment to permit removal of the control valve without draining the system d Strainers thermometers and pressure gauges are located between the gate valve and the equipment The following diagrams illustrate examples of piping layout Schematic Diagram For Mini Air Cooled Chiller Installation MAIN SUPPLY OVER FLOW PI...

Page 8: ...d and selected to comply with the local national codes of regulations This is also subject to the type of installation and conductors used The appropriate voltage range should be checked with label data on the unit Model UAHMM20AV1 UAHMM20AZV1 UAHMM25AV1 UAHMM25AZV1 UAHMM30AY1 UAHMM30AZY1 UAHMM40AY1 UAHMM40AZY1 Voltage Range 220V 240V 50Hz 380V 415V 3 50Hz Recommended Fuse A 10 10 Power Supply Cab...

Page 9: ... Parts Maintenance Procedures Period Fan Coil Unit Air Filter 1 Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water below 40 C with a neutral cleaning detergent 2 Rinse the filter well and dry before placing it back onto the unit 3 Do not use gasoline volatile substances or chemicals to clean the filter At least once every 2 weeks More frequently if necessary...

Page 10: ...taller 2 The air flow is too low The air filter is dirty The doors or windows are open The air suction and discharge are clogged The regulated temperature is not high enough 3 The remote control display is dim Battery flat The batteries are placed incorrectly 4 Discharge air flow has bad odor Odors may be caused by cigarettes smoke particles perfume etc which might have adhered onto the coil 5 Con...

Page 11: ......

Page 12: ...are for illustration purposes only Lot 60334 Persiaran Bukit Rahman Putra 3 Taman Perindustrian Bukit Rahman Putra 47000 Sungai Buloh Selangor Darul Ehsan Malaysia Head ofÞce Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo ofÞce JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global ...