Maximum circuit breaker is based on 225% maximum plus 100% of the rated
load amps for all loads included in the circuit, per circuit, per U.L. 1995 Fig.
36.2.
Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other
compressor RLAs + (# fans x each fan motor FLA)
6.4.3