Troubleshooting
SiUS12-928_A
117
Service Diagnosis
5.12 Compressor Lock
Remote
Controller
Display
E6
Outdoor Unit LED
Display
A
5
1
1
2
4
3
4
4
1
Method of
Malfunction
Detection
A compressor lock is detected by checking the compressor running condition through the position
detection circuit.
Malfunction
Decision
Conditions
Judging from the current waveform generated when high-frequency voltage is applied to the
compressor.
If the error repeats 16 times, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Compressor locked
Troubleshooting
Turn off the power. Disconnect the
harnesses U, V, and W.
(R11301)
Caution
NO
YES
YES
NO
NO
YES
Check with the inverter checker (
∗
).
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Correct the power supply or
replace the SPM or the
PM1.
(Replace the outdoor unit
PCB.)
∗
Inverter checker
Part No.: 1225477
Replace the compressor.
Replace it as required.
Replace the compressor.
Check the electronic
expansion valve.
Normal?
Emergency
stop without compressor
running?
System shut
down after errors repeated
several times?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for SUPER MULTI NX G Series
Page 1: ...SiUS12 928_A Applied Models Inverter Multi Heat Pump G Series J Series...
Page 7: ...SiUS12 928_A Table of Contents vi...
Page 10: ...SiUS12 928_A 1 List of Functions Part 1 List of Functions 1 Functions 3...
Page 11: ...SiUS12 928_A List of Functions 2...
Page 17: ...SiUS12 928_A Specifications 8...
Page 23: ...SiUS12 928_A Specifications Specifications 14...
Page 25: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram 16...
Page 37: ...SiUS12 928_A Function and Control 28...
Page 69: ...SiUS12 928_A Control Specification Function and Control 60...
Page 71: ...SiUS12 928_A Operation Manual 62...
Page 73: ...SiUS12 928_A Duct Free System Operation Manual 64 2 Duct Free System 2 1 Remote Controller...
Page 84: ...Duct Free System SiUS12 928_A 75 Operation Manual...
Page 85: ...SiUS12 928_A Duct Free System Operation Manual 76 2 8 TIMER Operation...
Page 86: ...Duct Free System SiUS12 928_A 77 Operation Manual...
Page 87: ...SiUS12 928_A Duct Free System Operation Manual 78 2 9 Note for Multi System...
Page 88: ...Duct Free System SiUS12 928_A 79 Operation Manual...
Page 97: ...SiUS12 928_A Slim Duct Built In System Operation Manual 88...
Page 99: ...SiUS12 928_A Service Diagnosis 90...
Page 169: ...SiUS12 928_A Removal Procedure 160...
Page 225: ...SiUS12 928_A Trial Operation and Field Settings 216...
Page 235: ...SiUS12 928_A Appendix 226...