Troubleshooting by Error Codes
SiUS281811EA
270
Part 6 Service Diagnosis
Reference
4.42 Inverter Compressor Overcurrent
Error Code
L8
Applicable
Models
All outdoor units
Method of Error
Detection
Error is detected by current flowing in the power transistor.
Error Decision
Conditions
Overload in the compressor is detected.
Supposed
Causes
Compressor overload
Broken wire inside compressor
Defective PCB
Disconnection of compressor
Troubleshooting
CHECK 4
Refer to page 295.
NO
YES
YES
NO
Check if the
compressor lead wires are
normal.
Insulation
resistance of the compressor
is 100 k
:
or below.
YES
NO
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Compressor coils are
disconnected.
Connect the compressor lead
wires then restart the operation.
CHECK 4
Check if the power transistor
is normal.
YES
Replace the compressor
lead wires.
Replace the inverter
compressor.
Replace the inverter
compressor.
Replace the
outdoor main PCB
(A1P).
NO
YES
Error code
L8
is
displayed again.
Continue the operation.
Inspection of the
compressor.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...