Troubleshooting by Remote Controller
SiUS281117
Service Diagnosis
159
2.40 Transmission Error (between Control and Inverter PCB)
Remote
Controller
Display
LC
Applicable
Models
RZR, RZQ
Method of Error
Detection
Check the communication state between inverter PCB and control PCB by micro-computer.
Error Decision
Conditions
When the correct communication is not carried out in certain period of time or longer
Supposed
Causes
Incorrect transmission wiring between control and inverter PCB/Insufficient contact in wiring
Defective outdoor unit PCB
Defective outdoor unit fan motor
External factor (Noise etc.)
Defective fan motor connector contact
Troubleshooting
Is "
E7
"
displayed on the
remote controller? (not
"
LC
")
Is the
connector for
the fan motor properly
connected to the indoor
unit PCB?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Disconnect the connection for
the fan motor, and turn ON
again.
Replace the outdoor unit PCB
(A1P).
Replace the fan motor.
Transmission error of the
inverter occurs due to the fan
motor error.
Connect correctly.
Caution
NO
YES
YES
NO