Troubleshooting by Remote Controller
SiUS281117
Service Diagnosis
113
2.9
Indoor Unit Fan Motor Abnormality
Remote
Controller
Display
A6
Applicable
Models
All indoor models
Method of Error
Detection
Detection of abnormal fan revolution by signal from the fan motor
Error Decision
Conditions
The error is generated when the fan revolution do not increase while the output voltage to the
fan is at its maximum.
Supposed
Causes
Disconnection, short circuit or disengagement of connector in fan motor harness
Defective fan motor (disconnection, poor insulation)
Abnormal signal from fan motor (defective circuit)
Defective Indoor unit PCB
Instantaneous fluctuation of power supply voltage
Fan motor lock
(Caused by motor or other external factors)
Fan does not turn due to a tangle of foreign matters.
Disconnection of the connector between the high-power PCB and the low-power PCB.