Field Setting
SiUS28-902_B
48
Test Operation
3. Field Setting
3.1
Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause error.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
3.1.1 Wired Remote Controller
Applicable Models
BRC1D71
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual for each optional accessory.
1. When in the normal mode, press the “
” button (
N
) for 4 seconds or more, and the
FIELD SETTING MODE is entered.
2. Select the desired MODE NO. with the “
” button (
O
).
3. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have been
selected), press the “
” button (
P
) and select the INDOOR UNIT NO. to be set. (This
operation is unnecessary when setting by group.)
4. Press the “
” upper button (
Q
) and select FIRST CODE NO.
5. Press the “
” lower button (
R
) and select the SECOND CODE NO.
6. Press the “
” button (
S
) once and the present settings are SET.
7. Press the “
” button (
T
) to return to the NORMAL MODE.
Example
When setting the filter sign time to “Filter Contamination Heavy” in all group unit setting, set the
Mode No. to “10”, first code No. to “0” and second code No. to “02”.
Model Series
FCQ
FHQ
FAQ
FTQ
Wired Remote Controller with
Weekly Schedule Timer
BRC1D71
Navigation Remote Controller
BRC1E71
TEST
SETTING
Unit NO.
UNIT NO.
MODE NO.
1 7
6
3
4
5
2
SECOND
CODE NO.
FIRST
CODE NO.
FIELD
SETTING
MODE
TEST
TEST