![Daikin SkyAir FHQ18PVJU Installation Manual Download Page 20](http://html1.mh-extra.com/html/daikin/skyair-fhq18pvju/skyair-fhq18pvju_installation-manual_2460087020.webp)
3
English
This air conditioner is an appliance that should not be
•
accessible to the general public.
The wall thickness of fi eld-installed pipes should be
•
selected in accordance with the relevant local, state,
and national regulations.
〈
Safety Precaution
〉
The PCI Data Station is a class A product. In a domestic
environment this product may cause radio interference in
which case the user may be required to take adequate mea-
sures.
INTRODUCTION
2.
Standard operation limit
2-1
The fi gures below assume following operating conditions for
indoor and outdoor units:
Equivalent pipe length ................ 25 ft.
Level difference .......................... 0 ft.
Cooling
Heating
<b>
B
<c>
A
C
D
<a>
0
5
59
115
41
50
50
43
70
95
81
50
23
77
60
67
82
57
A Outdoor temperature (°FDB)
B Indoor temperature (°FWB)
C Outdoor temperature (°FWB)
D Indoor temperature (°FDB)
Range for continuous operation
Range for pull down operation
Range for warming up operation
Range for operation
Technical specifi cations
2-2
(
∗
<a> and
∗
<b> in the table indicate the operating condition
(shown in the left fi gure).)
Model
RZQ18PVJU8
RZR18PVJU8
RZQ24PVJU8
RZR24PVJU8
RZQ30PVJU8
RZR30PVJU8
Precaution
Refrigerant
R410A
Power
208/230V 60Hz
[FAQ] Wall mounted
Cooling (MBh)
18.0
24.0
–
∗
<a>
Heating (MBh) (RZQ only)
20.0
26.0
–
∗
<b>
[FBQ] Ceiling mounted Duct
Cooling (MBh)
18.0
24.0
30.0
∗
<a>
Heating (MBh) (RZQ only)
20.0
27.0
34.0
∗
<b>
[FCQ] Ceiling mounted Cassette
Cooling (MBh)
18.0
24.0
30.0
∗
<a>
Heating (MBh) (RZQ only)
20.0
27.0
34.0
∗
<b>
[FHQ] Ceiling Suspended
Cooling (MBh)
18.0
24.0
30.0
∗
<a>
Heating (MBh) (RZQ only)
20.0
27.0
34.0
∗
<b>
(RZQ only)
[FTQ~PB] Air Handling Unit
Cooling (MBh)
Heating (MBh)
18.0
20.0
24.0
27.0
–
–
∗
<a>
∗
<b>
Dimensions
(inch)
30-5/16 × 35 7/16 × 12 5/8
H × W × D
Weight
(lb.)
150
Connections
Gas
(inch)
5/8
Liquid
(inch)
3/8
Electrical specifi cations
2-3
(
∗
<c> in the table indicate the operating condition (shown in
the left fi gure).)
Model
RZQ18PVJU8
RZR18PVJU8
RZQ24PVJU8
RZR24PVJU8
RZQ30PVJU8
RZR30PVJU8
Precaution
Power
Phase
1
~
Frequency
(Hz)
60
Voltage
(V)
208/230
Voltage
tolerance
(%)
±10
Max.Overcurrent
Protective device
(A)
20
Min. Circuit Amps.
(A)
16.5
∗
<c>
Compressor
Phase
3
~
Frequency
(Hz)
60
Voltage
(V)
208/230