14

E5

Compressor motor lock malfunction

E7

Outdoor fan motor lock malfunction
Outdoor fan instantaneous overcurrent malfunction

E9

Electronic expansion valve faulty (outdoor unit)

F3

Discharge pipe temperature abnormal (outdoor unit)

F6

The refrigerant is overcharged.

H9

Outdoor air thermistor faulty (outdoor unit)

J3

Discharge pipe thermistor faulty (outdoor unit)

J5

Suction pipe thermistor faulty (outdoor unit)

J6

Heat exchanger thermistor faulty (outdoor unit)

J9

Sensor for heat exchanger is fault.

JA

Sensor for high pressure is fault.

JC

Sensor for low pressure is fault.

L4

Overheated heat-radiating fi n (outdoor unit)

Inverter cooling defect.

L5

Instantaneous overcurrent (outdoor unit)

Possible earth fault or short circuit in the compressor 
motor.

L8

Electric thermal (outdoor unit)

Possible electrical overload in the compressor or cut 
line in the compressor motor.

L9

Stall prevention (outdoor unit)

Compressor possibly locked.

LC

Transmission malfunction between the outdoor control 
units’ inverters (outdoor unit)

P1

Open-phase (outdoor unit)

P3

PC board temperature sensor malfunction (outdoor 
unit)

P4

Heat-radiating fi n temperature sensor malfunction 
(outdoor unit)

PJ

Type set improper (outdoor unit)

Capacity data is wrongly preset. Or there is nothing 
programmed in the data hold IC.

U0

Suction pipe temperature abnormal

U2

Power source voltage malfunction

Includes the defect in K1M.

U3

The check operation has not performed.

U4
UF

Transmission error (indoor unit – outdoor unit)

Miswiring between indoor and outdoor units or 
malfunction of the PC board mounted on the indoor 
and the outdoor units.
If UF is shown, the wire between the indoor and 
outdoor units is not properly wired. Therefore, 
immediately disconnect the power supply and correct 
the wire. (The compressor and the fan mounted on the 
outdoor unit may start operation independent of the 
remote controller operation.) The power is not supplied 
to outdoor unit.

U9

Same transmission for in / outdoor unit is fault.

UA

Miss setting for multi system

Setting is wrong for selector switch of multi-system. 
(see switch SS2 on the main unit’s PC board)

01_EN_3PN06240-13M.indd   14

01_EN_3PN06240-13M.indd   14

12/25/2008   5:40:14 PM

12/25/2008   5:40:14 PM

Summary of Contents for SkyAir FCQ18PVJU

Page 1: ...lace for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce m...

Page 2: ...s and an asphyxiation hazard could occur leading to serious injury or death If the refrigerant gas leaks during installation ventilate the area immediately Refrigerant gas may produce toxic gas if it...

Page 3: ...uble may occur Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause m...

Page 4: ...ake noise Is the gas leak test finished It may result in insufficient cooling Is the unit fully insulated Condensate water may drip Does drainage flow smoothly Condensate water may drip Does the power...

Page 5: ...ension bolts for installation Check whether 3 the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit Installation pit...

Page 6: ...utdoor unit casing outlet Refer to the REFRIGERANT PIPING WORK Page 7 DRAIN PIPING WORK Page 8 and ELECTRIC WIRING WORK Page 9 After making an opening in the ceiling it may be neces sary to reinforce...

Page 7: ...center of the ceiling opening is indicated on the paper pattern for installation The center of the unit is indicated on the label attached to the unit and on the paper pattern for installation After...

Page 8: ...efore connecting The flare nuts used must be those included with the main body Over tightening may damage the flare and cause a refriger ant leakage Not recommended but in case of emergency You must u...

Page 9: ...inst condensate Improperly rigged pipe could lead to leak and eventually wet furniture and belongings Rig drain pipe 1 The diameter of the drain pipe should be greater than or equal to the diameter of...

Page 10: ...nlet lid length in Drain pipe Portable pump Inspection opening Service condensate outlet with rubber plug Use this outlet to condensate from the drain pan Bucket Adding water from inspection opening P...

Page 11: ...AND OTHER SMALL CREATURES FROM OUTSIDE Otherwise a short circuit may occur inside the control box L1 L2 Clamp A Transmission wire Remote controller wire Clip Power supply Transmission terminal block...

Page 12: ...smission wire Switch Fuse Indoor unit Remote controller When using 1 remote controller for 1 indoor unit 1 Normal operation L1L2 IN D OUT D F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 Power Supply 208 230V 60...

Page 13: ...ing must be made from the remote controller in accordance with the installation condition Setting can be made by changing the Mode No FIRST CODE NO and SECOND CODE NO For setting and operation refer t...

Page 14: ...that the indoor unit no with the trouble can be recog nized NOTE 2 With the wireless remote controller 2 Refer also to the operation manual attached to the wire less remote controller When the operat...

Page 15: ...malfunction between the outdoor control units inverters outdoor unit P1 Open phase outdoor unit P3 PC board temperature sensor malfunction outdoor unit P4 Heat radiating fin temperature sensor malfunc...

Page 16: ...3PN06240 13M EM08A095 0902 HT...

Reviews: