Remove the drain plug, the insulation tube, and the drain hose from the drain pan and replace.
•
(Refer to Fig. 8)
Connect the local refrigerant piping ahead of time, matching it to the liquid pipe and gas pipe marks en-
•
graved on the installation panel (accessory) (1).
< Replacing the drain hose and drain plug >
(1) Remove the drain plug and insulation tube.
(2) Remove the drain hose and replace onto the left side.
(3) Replace the drain plug and the insulation tube onto the right side.
Drain plug
Insulating tube
Fig. 8
Do not place lubricant (refrigerant oil) when inserting.
This may cause deterioration and water leaks.
Insert using a hexagon wrench (4mm).
Make sure
there are
no gaps.
Hook the indoor unit onto the installation panel. (Refer to Fig. 9)
(6)
Placing buffering material between the wall and the indoor unit at this time will make work easier.
•
Refrigerant piping
Be sure to pass all wires through
the wiring guide.
Tab
(There are 2 places.)
Wiring (locally procured)
Transmission wiring, Remote controller wiring
Wall
Installation panel
(accessory) (1)
Front panel
Front grill
Service lid
Place buffering material
Power supply wiring,
Ground wiring
Conduit
Hook the indoor unit hook onto the installation panel (1).
Fig. 9
For bottom-right and back-right piping
Pass the drain hose and the refrigerant piping to the wall.
•
Pass power supply wiring and ground wiring threaded through conduit (For connecting the con-
(7)
duit to the unit, see “8-1 HOW TO CONNECT WIRINGS”), and remote controller wiring through the
wiring guide in through the back of the indoor unit and to the front.