ESIE02–01
Overview of the heating mode functions
Part 2 – Functional Description
2–49
3
2
4
5
1
3.9
Motor Operated Valve Control
Applicable units
R(Y)P71-250B
Pump down
residual operation
The unit conducts a pump down residual operation after each compressor stop command. The
purpose of this function is to collect the refrigerant in the liquid receiver in order to prevent refrigerant
from remaining in the indoor heat exchanger.
Start-up control
When the compressor starts, a pump down operation is carried out in order to avoid liquid pumping.
The liquid receiver fills up and a minimum refrigerant amount is passed to the compressor. This
minimum refrigerant amount is required to avoid discharge pipe temperatures that are too high.
The opening degree of the expansion valve depends on the start-up number. If the first start-up fails,
the opening degree of the following start-up is adapted by the self-learning function.
Initial opening
degree
The initial opening degree of the outdoor expansion valve depends on the indoor and outdoor air
temperature. The calculation of the opening degree is made at a thermostat ON and at the end of a
defrosting cycle.
Opening degree:
Self-learning
function
When the system was stopped due to abnormal suction or discharge pressure, or due to a discharge
temperature that is too high, the expansion valve control tries to avoid the same breakdown. The
expansion valve increases the previous opening degree with 70 (in cooling mode) or 80 (in heating
mode) pulses at the next start-up.
There are maximum five start-up attempts. When the compressor stops again after the fifth start-up,
something is wrong with the unit and a unit check is necessary. The relevant error code appears on
the remote control.
Compressor
OFF
ON
EV
SV
Thermostat
Refrigerant
recuperation
0
480
OFF
ON
OFF
ON
Compressor
OFF
ON
EV
SV
Thermostat
1. Equalisation
2. Start-up control
3. Normal control
1
2
3
0
480
OFF
ON
OFF
ON
Summary of Contents for Sky Air R-407C
Page 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 2: ......
Page 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 4: ......
Page 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Page 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Page 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Page 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Page 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Page 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Page 110: ...ESIE02 01 1 94 Part 1 System Outline...
Page 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Page 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Page 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Page 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Page 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...