background image

Installation manual

7

How to use the stop valve

Use hexagonal wrenches 4 mm and 6 mm.

Opening the valve

1.

Place the hex wrench on the valve bar and turn counter-
clockwise.

2.

Stop when the valve bar no longer turns. It is now open.

Closing the valve

1.

Place the hex wrench on the valve bar and turn clockwise.

2.

Stop when the valve bar no longer turns. It is now closed.

Cautions for handling the valve cover

The valve cover is sealed where indicated by the arrow. 
Refer to the figure.
Take care not to damage it.

After operating the valve, be sure to tighten the valve cover
properly.

Check for refrigerant leakage after tightening the cap.

Cautions for handling service port

Always use a flexible charge hose with a push-rod and valve to
enable recovery of remaining refrigerant in the charge hose.

After the work, tighten the valve cover in place.
Tightening torque: 11.5~13.9 N•m

Precautions when connecting field piping and regarding 
insulation

Be careful not to let the indoor and outdoor branch piping come
into contact with the compressor terminal cover.
If the liquid-side piping insulation might come into contact with it,
adjust the height as shown in the figure below. Also, make sure
the field piping does not touch the bolts or outer panels of the
compressor.

When the outdoor unit is installed above the indoor unit the
following can occur:
The condensated water on the stop valve can move to the indoor
unit. To avoid this, please cover the stop valve with sealing
material.

If the temperature is higher than 30°C and the humidity is higher
than RH 80%, then the thickness of the sealing materials should
be at least 20 mm in order to avoid condensation on the surface
of the sealing.

Be sure to insulate the liquid and gas-side field piping and the
refrigerant branch kit.

(The highest temperature that the gas-side piping can reach is
around 120°C, so be sure to use insulating material which is
very resistant.)

Cautions for flare connection

Please refer to the table for the dimensions for processing flares
and for the tightening torques. (Too much tightening will end up
in splitting of the flare.)

If a torque wrench is not available, be aware that the tightening
torque may increase suddenly. Do not tighten nuts any further
than to the angle as listed.

When connecting the flare nut, coat the flare inner surface with
ether oil or ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.

After completing the installation, carry out a gas leak inspection
of the piping connections with nitrogen and such.

 

Closing direction

A

Liquid side

B

Gas side

Tightening torque

Liquid pipe

13.5~16.5 N•m

Gas pipe

22.5~27.5 N•m

A

B

Any exposed piping may cause condensation or burns
if touched.

Piping 

size

Flare nut 

tightening torque

A dimensions for 

processing flares 

(mm)

Flare shape

Ø6.4

15~17 N•m

8.7~9.1

Ø9.5

33~39 N•m

12.8~13.2

Ø12.7

50~60 N•m

16.2~16.6

Ø15.9

63~75 N•m

19.3~19.7

Piping size

Further tightening angle

Recommended arm 

length of tool

Ø6.4

60°~90°

150 mm

Ø9.5

200 mm

Ø12.7

30°~60°

250 mm

Ø15.9

300 mm

2

1

3

5

5

A

4

4

6

1

Compressor

2

Terminal cover

3

Indoor and outdoor 
field piping

4

Corking, etc.

5

Insulation material

6

Bolts

A

Be careful with pipe, 
bolt and outer panel 
connections

R=0.4~0.8

45

° ±

2

90

°±

2

A

Summary of Contents for Siesta AZQS71B2V1B

Page 1: ...INSTALLATION MANUAL AZQS71B2V1B AZQS100A7V1B AZQS125A7V1B AZQS140A7V1B AZQS100A7W1B AZQS125A7W1B AZQS140A7W1B Split System air conditioners...

Page 2: ...0 Hz 220 240 V R410A 1 2 4 5 6 3 1 3 2 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L...

Page 3: ...como se establece en A y es valorado positivamente por B de acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabel...

Page 4: ...ositivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet...

Page 5: ...lation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by quali ed personnel according to the local laws and regulations and this installatio...

Page 6: ...e uctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the relevant national and international codes it may b...

Page 7: ...he unit the fan can start rotating very fast until it breaks Refer to the gures for installation of this unit in a place where the wind direction can be foreseen Turn the air outlet side toward the bu...

Page 8: ...r example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical gures used in her...

Page 9: ...stallation impossible Installation shall be done by a licensed refrigeration technician the choice of materials and installation shall comply with the applicable national and international codes In Eu...

Page 10: ...end surfaces to prevent rusting Preventing foreign objects from entering Plug the pipe through holes with putty or insulating material procured locally to stop up all gaps as shown in the gure Insects...

Page 11: ...an 30 C and the humidity is higher than RH 80 then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing Be sure to insulate the...

Page 12: ...Evacuate the pipes and check vacuum 1 No pressure increase for 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen Never pressurize more than 4 0 MPa 3 Conduct leak test by applying soap w...

Page 13: ...Maximum total one way piping length of the table in paragraph Allowable pipe length and height difference on page 5 Table 2 Total charging amount unit kg NOTE National implementation of EU regulation...

Page 14: ...e terminal connectors When installing the earth leakage breaker make sure that it is compatible with the inverter resistant to high frequency electrical noise to avoid unnecessary opening of the earth...

Page 15: ...n Do not connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the belo...

Page 16: ...nctions according to the operation manual AZQS 71V1 100V1 125V1 140V1 100W1 125W1 140W1 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor uni...

Page 17: ...4 or L8 as an error code there is a possibility that either the stop valves are closed or that air inlet or air outlet are blocked If the error code U2 is displayed on the remote controller check for...

Page 18: ...discharge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 models only R5T Thermistor power module for...

Page 19: ......

Page 20: ...3P327449 6C...

Reviews: