Installation manual

1

AZQS7 AZQS100~14  AZQS100~140A7W1B

Split System air conditioners

4PW68422-1 – 03.2011

C

ONTENTS

Page

Safety considerations ........................................................................ 1

Before installation.............................................................................. 2

Selecting installation site................................................................... 3

Precautions on installation ................................................................ 4

Installation servicing space ............................................................... 4

Refrigerant pipe size and allowable pipe length ................................ 5

Precautions on refrigerant piping ...................................................... 6

Refrigerant piping.............................................................................. 6

Evacuating......................................................................................... 8

Charging refrigerant .......................................................................... 9

Electrical wiring work....................................................................... 10

Test operation.................................................................................. 12

Disposal requirements .................................................................... 13

Wiring diagram ................................................................................ 14

The English text is the original instruction. Other languages are
translations of the original instructions.

S

AFETY

 

CONSIDERATIONS

The precautions listed here are divided into the following two types.
Both cover very important topics, so be sure to follow them carefully.

Warning

The equipment is not intended for use in a potentially explosive
atmosphere.

For use of air-conditioning units in applications with temperature
alarm settings it is advised to foresee a delay of 10 minutes for
signalling the alarm in case the alarm temperature is exceeded.
The air-conditioning unit may stop for several minutes during
normal operation for "defrosting of the indoor unit" or when in
"thermostat-stop" operation.

Ask your dealer or qualified personnel to carry out installation work.
Do not install the machine by yourself.
Improper installation may result in water leakage, electric shocks
or fire.

Perform installation work in accordance with this installation
manual.
Improper installation may lead to water leakage, electric shocks
or fire.

Consult your local dealer regarding what to do in case of
refrigerant leakage. When the air conditioner is to be installed in
a small room, it is necessary to take proper measures so that
the amount of any leaked refrigerant does not exceed the
concentration limit in the event of a leakage. Otherwise, this may
lead to an accident due to oxygen depletion.

Be sure to use only the specified accessories and parts for
installation work.
Failure to use the specified parts may result in water leakage,
electric shocks, fire, or the unit falling.

Install the air conditioner on a foundation that can withstand its
weight.
Insufficient strength may result in the fall of equipment and
causing injury.

Carry out the specified installation work in consideration of strong
winds, typhoons, or earthquakes.
Improper installation work may result in accidents due to fall of
equipment.

Make certain that all electrical work is carried out by qualified
personnel according to the local laws and regulations and this
installation manual, using a separate circuit.
Insufficient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or fire.

Make sure that all wiring is secure, using the specified wires and
ensuring that external forces do not act on the terminal
connections or wires.
Incomplete connection or fixing may cause a fire.

When wiring between the indoor and outdoor units, and wiring
the power supply, form the wires so that the frontside panel can
be securely fastened.
If the frontside panel is not in place, overheat of the terminals,
electric shocks or a fire may be caused.

If refrigerant gas leaks during installation work, ventilate the
area immediately.
Toxic gas may be produced if refrigerant gas comes into contact
with fire.

After completing the installation work, check to make sure that
there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the room
and comes into contact with a source of fire, such as a fan
heater, stove or cooker.

Before touching electric terminal parts, turn off power switch.

Live parts can be easily touched by accident.
Never leave the unit unattended during installation or servicing
when the service panel is removed.

When planning to relocate former installed units, you must first
recover the refrigerant after the pumping-down operation. Refer
to chapter 

"Precaution for pumping-down operation" on page 10

.

Never directly touch any accidental leaking refrigerant. This
could result in severe wounds caused by frostbite.

AZQS71A2V1B
AZQS100A7V1B

AZQS100A7W1B

AZQS125A7V1B

AZQS125A7W1B

AZQS140A7V1B

AZQS140A7W1B

Split System air conditioners

Installation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

WARNING

If the warning is not observed, it may cause serious casualties.

CAUTION

If the caution is not observed, it may cause injury or damage to the 
equipment.

Summary of Contents for Siesta AZQS71A2V1B

Page 1: ...INSTALLATION MANUAL AZQS71A2V1B AZQS100A7V1B AZQS125A7V1B AZQS140A7V1B AZQS100A7W1B AZQS125A7W1B AZQS140A7W1B Split System air conditioners...

Page 2: ...0 Hz 220 240 V R410A 1 2 4 5 6 3 1 3 2 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L...

Page 3: ...positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurder...

Page 4: ...lation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the local laws and regulations and this installati...

Page 5: ...els of salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with...

Page 6: ...trong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be...

Page 7: ...pe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly INSTALLAT...

Page 8: ...L H 0 L 1 2H 150 250 1 2H L 200 300 H L Installation impossible Installation shall be done by a licensed refrigeration technician the choice of materials and installation shall comply with the applic...

Page 9: ...pair paint to the edge and the surrounding end surfaces to prevent rusting Preventing foreign objects from entering Plug the pipe through holes with putty or insulating material procured locally to st...

Page 10: ...ing material If the temperature is higher than 30 C and the humidity is higher than RH 80 then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the sur...

Page 11: ...edure for leak test Leak test must satisfy EN378 2 1 Evacuate the pipes and check vacuum 1 No pressure increase for 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen Never pressurize mor...

Page 12: ...relate to the refrigerant piping length as in Maximum total one way piping length of the table in paragraph Allowable pipe length and height difference on page 5 Table 2 Total charging amount unit kg...

Page 13: ...ide Make sure no external pressure is applied to the terminal connectors When installing the earth leakage breaker make sure that it is compatible with the inverter resistant to high frequency electri...

Page 14: ...asons be sure to observe the following instruction Do not connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When connecting wires of...

Page 15: ...e unit returns to normal operation 10 Check all functions according to the operation manual AZQS 71V1 100V1 125V1 140V1 100W1 125W1 140W1 Minimum circuit amps MCA a a Stated values are maximum values...

Page 16: ...ay have run out If the remote controller shows E3 E4 or L8 as an error code there is a possibility that either the stop valves are closed or that air inlet or air outlet are blocked If the error code...

Page 17: ...r discharge for V1 models only R3T Thermistor discharge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1...

Page 18: ......