5

Drain piping work

Installation of drain piping

Install the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.

Install the drain pipes.
- Keep piping as short as possible and slope it downwards at a 

gradient of at least 1/100 so that air may not remain trapped 
inside the pipe.

- Keep pipe size equal to or greater than that of the connecting 

pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer 
diameter).

- Push the supplied drain hose as far as possible over the 

drain socket.

- Tighten the metal clamp until the screw head is less than 

4 mm from the metal clamp part as indicated in the 
illustration.

- Wrap the supplied large sealing pad over the metal clamp 

and drain hose to insulate and fix it with clamps.

- Insulate the complete drain piping inside the building (field 

supply).

- If the drain hose cannot be sufficiently set on a slope, fit the 

hose with drain raising piping (field supply).

How to perform drain piping 

(See figure 10)

1

Connect the drain hose to the drain raising pipes, and insulate
them.

2

Connect the drain hose to the drain outlet on the indoor unit, and
tighten it with the clamp.

Precautions
- Install the drain raising pipes at a height of less than 625 mm.
- Install the drain raising pipes at a right angle to the indoor 

unit and no more than 300 mm from the unit.

- To prevent air bubbles, install the drain hose level or slightly 

tilted up (

75 mm).

- The drain pump mounted in this unit is the high lift type. The 

characteristic of this pump is that the higher the pump is the 
lower the drainage sound becomes. Therefore a drain pump 
height of 300mm is recommended.

Testing of drain piping

After piping work is finished, check if drainage flows smoothly.

Add approximately 1 l of water gradually through the air
discharge outlet. Check for water leaks.
Method of adding water. See 

figure 8

.

1

Hanging bar

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

3

Metal clamp (supplied with the unit)

4

Large sealing pad (supplied with the unit)

5

Drain piping (field supply)

1-1.5 m

1

2

1

5

2

3

4

4 mm

3

4

2

A

A'

A-A'

1

1

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

Installation

A (mm)

Rear suction installation

231

When canvas duct is installed

350-530

When air inlet panel is directly installed

231

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.

To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.

When unifying multiple drain pipes, install the
pipes as shown in 

figure 11

. Select converging

drain pipes whose gauge is suitable for the
operating capacity of the unit. 

1

T-joint converging drain pipes

1

Water inlet

2

Portable pump

3

Water inlet cover

4

Bucket (adding water through water inlet)

5

Drain outlet for maintenance (with rubber drain plug)

6

Refrigerant pipes

Summary of Contents for Siesta ADEQ100B2VEB

Page 1: ...INSTALLATION MANUAL FBQ35D2VEB FBQ50D2VEB FBQ60D2VEB FBQ71D2VEB FBQ100D2VEB FBQ125D2VEB FBQ140D2VEB Split System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...uerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Cer...

Page 4: ...alled at least 2 5 m from the floor Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install...

Page 5: ...he protection must comply with relevant European and national regulations 3 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If...

Page 6: ...duct according to the air inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape or something similar to prevent air escaping NOTE When installing...

Page 7: ...ea heater cooking stove etc Finally insulate as shown in the figures below Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying o...

Page 8: ...level or slightly tilted up 75 mm The drain pump mounted in this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefor...

Page 9: ...ically if the main power supply is turned off and then turned back on again Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the...

Page 10: ...e the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do...

Page 11: ...nd outlet is conform with the designed airflow rate Make sure the air conditioning unit is in fan operation mode Press and set the airflow adjustment button on the remote controller to change the airf...

Page 12: ...on Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation button and operate normally 7 Confirm function of unit according to the operation ma...

Page 13: ...CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR ADAPTOR FIELD WIRING BLK BLACK PNK PINK CONNECTOR BL...

Page 14: ......

Page 15: ...3 4 5 P1 P2 P1 P2 6 1 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 L N 3 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 6 L N L N 1 1 1 1 1 1 L N 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 16 1 4 2 3 5 7 8 11 12...

Page 16: ...4P391818 1B 2015 01 Copyright 2014 Daikin...

Reviews: