• Outdoor Unit • Outdoor units optimized for seasonal efficiency • RZQSG-LY1

1

2

• Split - Sky Air • Outdoor Unit

4

2

Specifications

 Notes

 (1) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions)
 (2) Energy label: scale from A (most efficient) to G (less efficient)
 (3) Cooling: indoor temp. 27ºCDB, 19ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m
 (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
 (5) Annual energy consumption is according to Energy labeling directive 2002/31/EC
 (6) SEER and SCOP are according to EN 14825

2-1 Nominal Capacity And Nominal Input

FBQ100C8 / RZQSG100LY1

FBQ125C8 / RZQSG125LY1

FBQ140C8 / RZQSG140LY1

Cooling capacity

Nom.

kW

9.5 (3)

12.0 (3)

13.4 (3)

Heating capacity

Nom.

kW

10.8 (4)

13.5 (4)

15.5 (4)

Power input

Cooling

Nom.

kW

2.87

3.74

4.44

Heating

Nom.

kW

2.96

3.85

4.54

EER

3.31

3.21

3.02

COP

3.65

3.51

3.41

SEER

5.11 (6)

4.35 (6)

-

SCOP

3.81 (6)

-

Annual energy consumption

kWh

1,435

1,870

2,220

Energy label

Cooling

A

B

Heating

A

B

2-1 Nominal Capacity And Nominal Input

FHQG100C / RZQSG100LY1

FHQG125C / RZQSG125LY1

FHQG140C / RZQSG140LY1

Cooling capacity

Nom.

kW

9.5 (3)

12.0 (3)

13.4 (3)

Heating capacity

Nom.

kW

10.8 (4)

13.5 (4)

15.5 (4)

Power input

Cooling

Nom.

kW

2.96

4.15

4.45

Heating

Nom.

kW

2.99

3.73

4.54

EER

3.21

2.89

3.01

COP

3.61

3.62

3.41

SEER

5.11 (6)

4.61 (6)

-

SCOP

3.80 (6)

3.81 (6)

-

Annual energy consumption

kWh

1,480

2,075

2,225

Energy label

Cooling

A

C

B

Heating

A

B

2-1 Nominal Capacity And Nominal Input

FDQ125C / RZQSG125LY1

Cooling capacity

Nom.

kW

12.0 (3)

Heating capacity

Nom.

kW

13.5 (4)

Power input

Cooling

Nom.

kW

3.74

Heating

Nom.

kW

3.85

EER

3.21

COP

3.51

SEER

4.35 (6)

SCOP

3.81 (6)

Annual energy consumption

kWh

1,870

Energy label

Cooling

A

Heating

B

Summary of Contents for RZQSG100LY1

Page 1: ...RZQSG LY1 Technical Data E E D E N 1 2 1 0 0 O u t d o o r u n i t s o p t i m i z e d f o r s e a s o n a l e f f i c i e n c y Air Conditioners...

Page 2: ...bles 11 Heating Capacity Tables 14 Capacity Correction Factor 17 7 Dimensional drawings 18 Dimensional Drawings 18 8 Centre of gravity 19 Centre of Gravity 19 9 Piping diagrams 20 Piping Diagrams 20 P...

Page 3: ...ives an indication on how efficient an air conditioner operates over an entire heating or cooling season Re use of existing R 22 or R 407C technology The use of inverter type outdoor units results in...

Page 4: ...4 15 5 4 Power input Cooling Nom kW 2 88 3 74 4 45 Heating Nom kW 3 05 3 96 4 54 EER 3 30 3 21 3 01 COP 3 54 3 41 SEER 5 11 6 SCOP 3 80 6 3 81 6 Annual energy consumption kWh 1 440 1 870 2 225 Energy...

Page 5: ...Heating capacity Nom kW 10 8 4 13 5 4 15 5 4 Power input Cooling Nom kW 2 87 3 74 4 44 Heating Nom kW 2 96 3 85 4 54 EER 3 31 3 21 3 02 COP 3 65 3 51 3 41 SEER 5 11 6 4 35 6 SCOP 3 81 6 Annual energy...

Page 6: ...Anti corrosion treatment PE Fan Type Propeller fan Discharge direction Horizontal Quantity 1 2 Air flow rate Cooling Nom m min 76 77 83 Super low m min cfm Heating Nom m min 83 62 Super low m min cfm...

Page 7: ...ctions Liquid Quantity 1 Type Flare connection OD mm 9 52 Gas Quantity 1 Type Flare connection OD mm 15 9 Drain Quantity 5 Type Hole ID mm OD mm 26 Piping length OU IU Min m 5 Max m 50 System Equiva l...

Page 8: ...3 1 3 Split Sky Air Outdoor Unit 7 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 3 Electrical data 3 1 Electrical Data...

Page 9: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 3 Split Sky Air Outdoor Unit 8 3 Electrical data 3 1 Electrical Data...

Page 10: ...3 1 4 Split Sky Air Outdoor Unit 9 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 4 Options 4 1 Options...

Page 11: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 5 Split Sky Air Outdoor Unit 10 5 Combination table 5 1 Combination Table...

Page 12: ...3 1 6 Split Sky Air Outdoor Unit 11 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 13: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 6 Split Sky Air Outdoor Unit 12 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 14: ...3 1 6 Split Sky Air Outdoor Unit 13 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 15: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 6 Split Sky Air Outdoor Unit 14 6 Capacity tables 6 2 Heating Capacity Tables...

Page 16: ...3 1 6 Split Sky Air Outdoor Unit 15 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 6 Capacity tables 6 2 Heating Capacity Tables...

Page 17: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 6 Split Sky Air Outdoor Unit 16 6 Capacity tables 6 2 Heating Capacity Tables...

Page 18: ...3 1 6 Split Sky Air Outdoor Unit 17 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 6 Capacity tables 6 3 Capacity Correction Factor...

Page 19: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 7 Split Sky Air Outdoor Unit 18 7 Dimensional drawings 7 1 Dimensional Drawings...

Page 20: ...3 1 8 Split Sky Air Outdoor Unit 19 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 8 Centre of gravity 8 1 Centre of Gravity...

Page 21: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 9 Split Sky Air Outdoor Unit 20 9 Piping diagrams 9 1 Piping Diagrams...

Page 22: ...3 1 9 Split Sky Air Outdoor Unit 21 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 9 Piping diagrams 9 2 Piping Diagram Twin Application...

Page 23: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 9 Split Sky Air Outdoor Unit 22 9 Piping diagrams 9 3 Piping Diagram Triple Application...

Page 24: ...3 1 9 Split Sky Air Outdoor Unit 23 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 9 Piping diagrams 9 4 Piping Diagram Double Twin Application...

Page 25: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 10 Split Sky Air Outdoor Unit 24 10 Wiring diagrams 10 1 Wiring Diagrams Three Phase...

Page 26: ...3 1 11 Split Sky Air Outdoor Unit 25 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 11 Sound data 11 1 Sound Power Spectrum...

Page 27: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 11 Split Sky Air Outdoor Unit 26 11 Sound data 11 2 Sound Pressure Spectrum Cooling...

Page 28: ...3 1 11 Split Sky Air Outdoor Unit 27 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 11 Sound data 11 3 Sound Pressure Spectrum Heating...

Page 29: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 11 Split Sky Air Outdoor Unit 28 11 Sound data 11 4 Sound Pressure Spectrum Quiet Mode...

Page 30: ...3 1 12 Split Sky Air Outdoor Unit 29 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 12 Installation 12 1 Installation Method...

Page 31: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 12 Split Sky Air Outdoor Unit 30 12 Installation 12 1 Installation Method...

Page 32: ...3 1 13 Split Sky Air Outdoor Unit 31 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 13 Operation range 13 1 Operation Range...

Page 33: ...ted by Daikin Europe N V Daikin s unique position as a manufacturer of air conditioning equipment compressors and refrigerants has led to its close involvement in environmental issues For several year...

Reviews: