RZQS71~125B7V3
Split System air conditioners
4PW32097-1

Installation manual

4

7

If you install the unit on a building frame, please install a
waterproof plate (within 150 mm of the underside of the unit) or
use a drain plug kit (option) in order to avoid the drainwater
dripping. (See figure).

P

RECAUTIONS

 

ON

 

INSTALLATION

Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.

In accordance with the foundation drawing in the figure, fix the
unit securely by means of the foundation bolts. (Prepare four
sets of M12 foundation bolts, nuts and washers each which are
available on the market.)

It is best to screw in the foundation bolts until their length are
20 mm from the foundation surface.

Installation method for prevention of falling over

If it is necessary to prevent the unit from falling over, install as shown
in the figure.

prepare all 4 wires as indicated in the drawing

unscrew the top plate at the 4 locations indicated A and B

put the screws through the nooses and screw them back tight

A

location of the 2 fixation holes on the front side of the unit

B

location of the 2 fixation holes on the rear side of the unit

C

wires: field supply

Drain pipe disposal

If drain pipe disposal from the outdoor unit causes trouble (for
example, if the drain water may splash on people) provide the
drain piping using a drain socket (optional).

Make sure the drain works properly.

I

NSTALLATION

 

SERVICING

 

SPACE

The numerical figures used in here represent the dimensions for the
71-100-125 class models. Figures between (  ) indicate the
dimensions for the 125 class models. (Unit: mm)

(Refer to 

"Precautions on installation" on page 4

)

Precaution

(A) In case of non-stacked installation 

(See figure 1)

(B) In case of stacked installation

1.

In case obstacles exist in front of the outlet side.

2.

In case obstacles exist in front of the air inlet.

Do not stack more than one unit.

About 100 mm is required as the dimension for laying the upper
outdoor unit's drain pipe. Get the portion A sealed so that air from the
outlet does not bypass.

(C) In case of multiple-row installation (for roof top use, etc.)

1.

In case of installing one unit per row.

Discharge side

Bottom view (mm)

Drain hole

20

140

117

219

289

350

(345-355)

47

140

620

614

423

A

B

C

C

B

A

A

Suction side obstacle

Obstacle is present

Discharge side obstacle

1

In these cases, close the 
bottom of the installation 
frame to prevent the 
discharged air from 
being bypassed

Left side obstacle

Right side obstacle

2

In these cases, only 2 
units can be installed.

Top side obstacle

This situation is not 
allowed

1000

100

A

200

(300)

100

A

500

(1000)

100

(200)

1000

(2000)

50

(100)

Summary of Contents for RZQS71B7V3

Page 1: ...INSTALLATION MANUAL RZQS71B7V3 RZQS100B7V3 RZQS125B7V3 Split System air conditioners...

Page 2: ...7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B...

Page 3: ...u condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on va...

Page 4: ...on may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire Whe...

Page 5: ...rding to national regulations Do not connect the earth wire to gas or water pipes lightning conductor or telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explos...

Page 6: ...ration of the operational capacity Frequent frost acceleration in heating operation Disruption of operation due to rise of high pressure When a strong wind blows continuously on the face of the unit t...

Page 7: ...pe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain w...

Page 8: ...e sizes must have the same size as the connected indoor units pipe sizes Branch see marking on figures 3 4 and 5 Selection of branch pipe L A L H 0 L 1 2H 150 250 1 2H L 200 300 H L Installation impos...

Page 9: ...nch pipe to the indoor unit should be as short as possible Try to keep lengths of both branch pipes to the indoor unit equal REFRIGERANT PIPING Field pipes can be installed in four directions Figure F...

Page 10: ...r to the figure Take care not to damage it After operating the valve be sure to tighten the valve cover properly Check for refrigerant leakage after tightening the cap Cautions for handling service po...

Page 11: ...f oxidised film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal operation When brazing pipes however do not use oxidation preven...

Page 12: ...0 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Total additional charge amount R R1 R2 kg Table 2 Length unit m additional charging of refrigerant unit kg Example 1 1 G1 L1 35 m G2 L2 L3 7...

Page 13: ...e bundled cables into a unit Fix cables so that cables do not make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in the figure be...

Page 14: ...wiring works Form the wires and fix the cover firmly so that the cover may be fit in properly Precautions on wiring of power supply and inter unit wiring Use a round crimp style terminal for connectio...

Page 15: ...pt displaying the heating symbol all the time and the unit will switch to heating operation automatically after elapse of that time 2 In case you cannot operate the unit in test run mode for any unusu...

Page 16: ...r code U4 or UF is displayed on the remote controller check the inter unit branch wiring connection The reversed phase protection detector of this product only works during the initialisation stage af...

Page 17: ...r air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor low S1PH Pressure switch high S1PL Pres...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW32097 1...

Reviews: