3. Field Setting from Outdoor Unit PCB
3.1
Location of DIP Switch and BS Button
Various settings are available by using the DIP switches and the BS buttons on the PCB.
*1. Factory settings: "OFF" and "HEAT"
Note:
BS button (Pump down / Forced defrosting)
Pressing the BS button forcibly operates the air conditioner in the cooling mode.
1. To conduct a pump-down operation (sending refrigerant to outdoor unit), press the BS
button to forcibly operate the equipment in the cooling mode, then operate the unit for about
1 minute to stabilize the system. After stabilizing system, close the liquid pipe stop valve on
the outdoor unit, and after the pressure decreases and the low pressure sensor activates,
close the gas pipe stop valve.
2. Forced defrost
To activate the defrost operation during the heating operation, press the BS button. This will
activate the forced defrost operation (cooling operation).
When the defrost cancel conditions are met, the equipment automatically switches off the
defrost operation.
X205A
H1P
H2P
H3P
H4P
H5P
H6P
H7P
COOL
ON
HEAT
OFF
ON
1
2
2
1
BS2
BS1
BS3
BS4
Dip Switch
A2P
MODE
MODE
SET
RETURN
PUMPDOWN
TEST
HWL
L.N.O.P
DEMAND
Display Lamp
BS Button
Display
Function or Operating Procedure
Symbol
Name
Display
Lamp
H1P
MODE
During "Setting mode 1," the lamp is
OFF (
h
).
During "Monitor mode," the lamp
blinks (
l
).
H2P
TEST
During test operation in "Setting
mode 1," the lamp is ON (
k
).
During "Monitor mode," the lamp is
OFF (
h
).
H3P
HWL
When an error occurs during "Setting
mode 1," the lamp turns ON (
k
).
H4P
L.N.O.P
During "Setting mode 1," low noise
level is displayed.
During "Monitor mode," various
combinations of the lamp indicate
the following conditions:
• Indication of oil return operation
• Indication of outdoor unit class
• Indication of error code (the latest
and up to 2 cycles before)
• Indication of causes of stepping-
down
H5P
H6P
DEMAND
During "Setting mode 1," demand
level is displayed.
H7P
BS
Button
BS1
MODE
Used to change "Setting mode".
BS2
SET
Used to change "Setting item" and "Setting condition".
BS3
RETURN
Used to decide "Setting item" and "Setting condition".
BS4
PUMP DOWN
Used for pump down operation, forced oil return operation and forced
defrost operation.
Dip
Switch
DS1-1
ON
EMERGENCY
Switch from "OFF" to "ON" for emergency operation (forced operation).
OFF(*1)
DS1-2
COOL
Maintain "HEAT" in case of heating in emergency operation, and switch to
"COOL" in case of cooling in emergency operation.
HEAT(*1)
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...