• Split - Sky Air • Outdoor Unit

5

• Outdoor Unit • Outdoor units optimized for seasonal efficiency • RZQG-LY1

2

Specifications

 Notes

 (1) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions)
 (2) Energy label: scale from A (most efficient) to G (less efficient)
 (3) Cooling: indoor temp. 27ºCDB, 19ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m
 (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
 (5) Annual energy consumption is according to Energy labeling directive 2002/31/EC
 (6) SEER and SCOP are according to EN 14825

2-1 Nominal Capacity And Nominal Input

FUQ71B8/RZQG71LY1

FUQ100B8/ RZQG100LY1

FUQ125B8/ RZQG125LY1

Cooling capacity

Nom.

kW

6.8 (3)

9.5 (3)

12.0 (3)

Heating capacity

Nom.

kW

7.5 (4)

10.8 (4)

13.5 (4)

Power input

Cooling

Nom.

kW

1.68

2.46

3.54

Heating

Nom.

kW

1.84

2.73

3.95

EER

4.05

3.86

3.39

COP

4.08

3.95

3.42

SEER

5.25 (6)

4.67 (6)

4.41 (6)

SCOP

3.89 (6)

4.02 (6)

4.09 (6)

Annual energy consumption

kWh

840

1,230

1,770

Energy label

Cooling

A

Heating

A

B

2-2 Technical Specifications

RZQG71LY1

RZQG100LY1

RZQG125LY1

RZQG140LY1

Capacity control

Method

Inverter controlled

Casing

Colour

Ivory white

Material

Painted galvanized steel plate

Dimensions

Unit

Height

mm

990

1,430

Width

mm

940

Depth

mm

320

Packed unit

Height

mm

1,170

1,610

Width

mm

1,015

Depth

mm

422

Weight

Unit

kg

80

101

Packed unit

kg

91

114

Heat exchanger

Length

mm

904

Rows

Quantity

2

Fin pitch

mm

1.4

Passes

Quantity

12

16

Face area

0.87

1.273

Stages

Quantity

44

64

Empty tubeplate 
hole

Quantity

0

Tube type

ø7 Hi-XSL

Fin

Type

WF fin

Treatment

Anti-corrosion treatment (PE)

Fan

Type

Propeller fan

Discharge direction

Horizontal

Quantity

1

2

Air flow rate

Cooling Nom.

m³/min

59

70

84

Super 
low

m³/min

-

cfm

-

Heating Nom.

m³/min

49

62

Super 
low

m³/min

-

cfm

-

Summary of Contents for RZQG-LY1

Page 1: ...RZQG LY1 Technical Data E E D E N 1 2 1 0 0 O u t d o o r u n i t s o p t i m i z e d f o r s e a s o n a l e f f i c i e n c y Air Conditioners...

Page 2: ...bles 13 Heating Capacity Tables 17 Capacity Correction Factor 21 7 Dimensional drawings 22 Dimensional Drawings 22 8 Centre of gravity 23 Centre of Gravity 23 9 Piping diagrams 24 Piping Diagrams 24 P...

Page 3: ...icient an air conditioner operates over an entire heating or cooling season Seasonal smart series already comply with EU s 2014 Eco Design requirements Suits computer room applications EDP Re use of e...

Page 4: ...0 3 13 4 3 Heating capacity Nom kW 7 5 4 10 8 4 13 5 4 15 5 4 Power input Cooling Nom kW 2 01 2 45 3 22 4 17 Heating Nom kW 1 89 2 60 3 72 4 30 EER 3 39 3 87 3 73 3 21 COP 3 97 4 15 3 63 3 61 SEER 5 8...

Page 5: ...QG125LY1 FVQ140C RZQG140LY1 Cooling capacity Nom kW 6 8 3 9 5 3 12 0 3 13 4 3 Heating capacity Nom kW 7 5 4 10 8 4 13 5 4 15 5 4 Power input Cooling Nom kW 2 02 2 49 3 74 4 17 Heating Nom kW 2 06 2 61...

Page 6: ...8 4 13 5 4 Power input Cooling Nom kW 1 68 2 46 3 54 Heating Nom kW 1 84 2 73 3 95 EER 4 05 3 86 3 39 COP 4 08 3 95 3 42 SEER 5 25 6 4 67 6 4 41 6 SCOP 3 89 6 4 02 6 4 09 6 Annual energy consumption k...

Page 7: ...Heating Ambient Min CWB 20 0 Max CWB 15 5 Refrigerant Type R 410A Charge kg 2 9 4 0 Control Expansion valve electronic type Circuits Quantity 1 Refrigerant oil Type FVC50K Charged volume l 0 9 1 35 P...

Page 8: ...the limits for harmonic currents produced by equipment connected to public low voltage system with input current 16A and 75A per phase 5 Short circuit power 2 3 Electrical Specifications RZQG71LY1 RZQ...

Page 9: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 3 Split Sky Air Outdoor Unit 8 3 Electrical data 3 1 Electrical Data...

Page 10: ...3 1 3 Split Sky Air Outdoor Unit 9 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 3 Electrical data 3 1 Electrical Data...

Page 11: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 4 Split Sky Air Outdoor Unit 10 4 Options 4 1 Options...

Page 12: ...3 1 5 Split Sky Air Outdoor Unit 11 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 5 Combination table 5 1 Combination Table...

Page 13: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 5 Split Sky Air Outdoor Unit 12 5 Combination table 5 1 Combination Table...

Page 14: ...3 1 6 Split Sky Air Outdoor Unit 13 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 15: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 6 Split Sky Air Outdoor Unit 14 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 16: ...3 1 6 Split Sky Air Outdoor Unit 15 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 17: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 6 Split Sky Air Outdoor Unit 16 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 18: ...3 1 6 Split Sky Air Outdoor Unit 17 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 6 Capacity tables 6 2 Heating Capacity Tables...

Page 19: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 6 Split Sky Air Outdoor Unit 18 6 Capacity tables 6 2 Heating Capacity Tables...

Page 20: ...3 1 6 Split Sky Air Outdoor Unit 19 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 6 Capacity tables 6 2 Heating Capacity Tables...

Page 21: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 6 Split Sky Air Outdoor Unit 20 6 Capacity tables 6 2 Heating Capacity Tables...

Page 22: ...3 1 6 Split Sky Air Outdoor Unit 21 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 6 Capacity tables 6 3 Capacity Correction Factor...

Page 23: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 7 Split Sky Air Outdoor Unit 22 7 Dimensional drawings 7 1 Dimensional Drawings...

Page 24: ...3 1 8 Split Sky Air Outdoor Unit 23 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 8 Centre of gravity 8 1 Centre of Gravity...

Page 25: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 9 Split Sky Air Outdoor Unit 24 9 Piping diagrams 9 1 Piping Diagrams...

Page 26: ...3 1 9 Split Sky Air Outdoor Unit 25 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 9 Piping diagrams 9 2 Piping Diagram Twin Application...

Page 27: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 9 Split Sky Air Outdoor Unit 26 9 Piping diagrams 9 3 Piping Diagram Triple Application...

Page 28: ...3 1 9 Split Sky Air Outdoor Unit 27 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 9 Piping diagrams 9 4 Piping Diagram Double Twin Application...

Page 29: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 10 Split Sky Air Outdoor Unit 28 10 Wiring diagrams 10 1 Wiring Diagrams Three Phase...

Page 30: ...3 1 11 Split Sky Air Outdoor Unit 29 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 11 Sound data 11 1 Sound Power Spectrum...

Page 31: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 11 Split Sky Air Outdoor Unit 30 11 Sound data 11 2 Sound Pressure Spectrum Cooling...

Page 32: ...3 1 11 Split Sky Air Outdoor Unit 31 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 11 Sound data 11 3 Sound Pressure Spectrum Heating...

Page 33: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 11 Split Sky Air Outdoor Unit 32 11 Sound data 11 4 Sound Pressure Spectrum Quiet Mode...

Page 34: ...3 1 12 Split Sky Air Outdoor Unit 33 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 12 Installation 12 1 Installation Method...

Page 35: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 1 12 Split Sky Air Outdoor Unit 34 12 Installation 12 1 Installation Method...

Page 36: ...3 1 13 Split Sky Air Outdoor Unit 35 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQG LY1 13 Operation range 13 1 Operation Range...

Page 37: ...ted by Daikin Europe N V Daikin s unique position as a manufacturer of air conditioning equipment compressors and refrigerants has led to its close involvement in environmental issues For several year...

Reviews: