Installation manual
7
RZQ7 RZQ100~14 RZQ100~140B9W1B
Split System air conditioners
4PW60930-1
■
In case of simultaneous operating system
-
Upward and downward piping should be performed at the
main piping line.
-
Use branch piping kit (optional) for branching refrigerant
pipes.
Precautions to be taken. (For details, refer to the manual attached to
branch piping kit.)
-
Install the branch pipes horizontally (with a maximum
inclination of 15°) or vertically.
-
Length of branch pipe to the indoor unit should be as short as
possible.
-
Try to keep lengths of both branch pipes to the indoor unit
equal.
■
When using existing refrigerant piping
Pay attention to the following points when using existing
refrigerant piping
■
Perform a visual check on quality of residual oil in existing
refrigerant piping.
This check is extremely important because using existing
piping with deteriorated oil will cause compressor
breakdown.
- Put some residual oil of the pipes you want to reuse on a
piece of white paper or on the white surface of an oil
checking reference card and compare that oil colour with
the circled colour of the oil checking reference card.
- If oil colour is identical to the circled colour or darker,
replace the piping, install new piping or clean the piping
thoroughly.
- If oil colour is lighter, the pipes can be reused without
cleaning.
An oil checking reference card is indispensable for such
evaluation and can be obtained at your dealer.
■
In the following situations, the existing piping should not be
re-used and new piping should be installed.
- If the previously used model had problems with its
compressor (this might cause oxidised coolant oil, scale
residue and other adverse effects).
- If the indoor or outdoor units were disconnected from the
piping for a long period of time (water or dirt might have
gotten into the piping).
- If copper piping is corroded.
■
Flares should not be re-used but rather new ones made in
order to prevent leaks.
■
Check welded connections for gas leaks, if the local piping
has welded connections.
■
Replace deteriorated insulation with new material.
R
EFRIGERANT
PIPING
■
Field pipes can be installed in four directions.
Figure - Field pipes in four directions
■
Cutting out the two slits makes it possible to install as shown in
the
figure "Field pipes in four directions"
(Use a metal saw to cut out the slits.)
■
To install the connecting pipe to the unit in a downward direction,
make a knockout hole by penetrating the centre area around the
knockout hole using a
Ø
6 mm drill. (See
■
After knocking out the knock-out, it is recommended to apply
repair paint to the edge and the surrounding end surfaces to
prevent rusting.
Preventing foreign objects from entering
Plug the pipe through-holes with putty or insulating material
(procured locally) to stop up all gaps, as shown in the figure.
Insects or small animals entering the outdoor unit may cause a short
circuit in the electrical box.
Cautions for handling stop valve
■
The stop valves for indoor-outdoor connecting piping are closed
at shipment from the factory.
The names of parts of the stop valve are shown in the figure.
1
Drill
2
Centre area around knockout hole
3
Knockout hole
4
Slit
5
Connecting pipe
6
Bottom frame
7
Front plate
8
Pipe outlet plate
9
Screw front plate
10
Pipe outlet plate screw
A
Forward
B
Backward
C
Sideways
D
Downward
1
Putty or insulating material
(produced locally)
Make sure to keep the valve open during operation.
1
Service port
2
stop valve
3
Field piping connection
4
Valve cover
4
4
3
2
1
7
8
9
10
A
D
C
B
5
6
1
3
4
1
2