17
|
Piping installation
Installer and user reference guide
79
RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546228-1C – 2021.11
17.1.7 Piping length: VRV DX and Hydrobox
For system containing VRV DX indoor units and Hydrobox:
System setup
Example
Description
Example 1
a
A
h
i
j
k
l
m
n
B
C
D
E
F
G
p
b
c
d
e
f
1
2
3
4
5
6
7
8
g
H1
H2
Branch with refnet joint
Example 2
a
b
c
d
e
f
i
k
j
g
h
A
B
1
2
3
4
5
6
7 8
H1
H2
Branch with refnet joint
and refnet header
Example 3
a
c
b
d
e
f
i
g
h
1
2
3
4
5
6
7
8
H1
H2
Branch with refnet header
1~7
VRV DX indoor units
8
Hydrobox unit (HXY080/125)
Maximum allowable length
Between outdoor and indoor units.
Actual piping length
135 m
Example 1:
▪
a+b+c+d+e+f+g+p≤135 m
▪
a+b+c+d+k≤135 m
Example 2:
▪
a+i+k≤135 m
▪
a+b+e≤135 m
Example 3:
▪
a+i≤135 m
▪
a+d≤135 m
Equivalent length
(a)
160 m
Total piping length
300 m
Example 3:
▪
a+b+c+d+e+f+g+h+i≤300 m
(a)
Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes of equivalent piping length, not for refrigerant charge calculations).
Maximum allowable height difference (on Hydrobox indoor unit)
H1
≤50 m (40 m) (if outdoor is located below indoor units)
H2
≤15 m