• Outdoor Units • R-410A • RYN-E3V1B
1
2
• Split Sky Air • Outdoor Units
3
2
Specifications
Compressor
Quantity
1
1
Motor
Model
2YC36BXD#A
Type
Hermetically sealed swing compressor
Motor
Output
W
1100
1100
Operation
Range
Cooling
Min
°
CDB
-10.0
-10.0
Max
°
CDB
46.0
46.0
Heating
Min
°
CWB
-15
-15
Max
°
CWB
18
18
Sound Level
(nominal)
Cooling
Sound
Power
dBA
61.0
63.0
Sound
Pressure
dBA
47.0
49.0
Heating
Sound
Pressure
dBA
48.0
49.0
Refrigerant
Type
R-410A
Charge
kg
1.5
1.5
Refrigerant Oil Type
FVC50K
Charged Volume
l
0.65
065
Piping
connections
Liquid (OD)
Diameter
(OD)
mm
6.35
6.35
Gas
Diameter
(OD)
mm
12.7
12.7
Drain
Diameter
(OD)
mm
18
18
Piping Length
Maximum m
30
30
Additional Refrigerant
Charge
kg/m
0.02/>10m
Max. internunit level
difference
m
20.0
20.0
Heat Insulation
Both liquid and gas pipes
Standard
Accessories
Item
Drain plug
Quantity
1
1
Item
Installation manual
Quantity
1
1
Notes
Nominal cooling capacities are based on : indoor temperature : 270CDB, 190CWB, outdoor temperature : 350CDB,
equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 200CDB, outdoor temperature : 70CDB, 60CWB,
equivalent refrigerant piping : 7.5m, level difference : 0m
Sound levels are measured in an anechoic room
Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details,
please refer to sound level drawings of this chapter.
The sound power level is an absolute value indicating the power which a sound source generates.
2-3 ELECTRICAL SPECIFICATIONS
RYN50E3V1B
RYN60E3V1B
Power Supply
Name
V1
Phase
1
1
Frequency
Hz
50
50
Voltage
V
220-240
Voltage range
Minimum V
-10%
Maximum V
+10%
Current
Nominal
running current
(RLA)
Cooling
(A)
A
6.75
8.62
Heating
(A)
A
6.94
8.80
Starting current (cooling/
heating)
A
7.1
9.0
Z-max
List
No requirements
2-2 TECHNICAL SPECIFICATIONS
RYN50E3V1B
RYN60E3V1B