![background image](http://html1.mh-extra.com/html/daikin/ry71kv1/ry71kv1_service-manual_2459991005.webp)
Si211311E
Procedure to Remove Outdoor Unit Fan and Fan Motor
Removal Procedure
3
2. Procedure to Remove Outdoor Unit Fan and Fan
Motor
Procedure
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
∗
Remove the front piping
cover, etc., according to the
procedure for removing the
external casing.
1
Remove the 4 screws
and disconnect the 8
tabs fastening the air
discharge grille on the
top/bottom and left/
right, and remove the
air discharge grille.
2
Remove the fan clamp
fastening the propeller
fan; remove the nut and
washer.
Note:
The fan motor’s lead wire
cannot be disconnected as is.
You must first remove the screw
on the right side of the front
casing (1).
3
Disconnect the motor
connector from the
PCB’s wiring connector,
and remove the
condenser.
Connector
Condenser