5 Installation
Installation and operation manual
17
RXYSQ4~6TAY1B
VRV IV-S system air conditioner
4P482256-1 – 2017.03
5.7.3
Guidelines when connecting the electrical
wiring
Tightening torques
Wiring
Screw size
Tightening torque
(N•m)
Power supply wiring
(power
shielded ground)
M5
2.2~2.7
Transmission wiring
M3.5
0.8~0.97
5.7.4
To connect the electrical wiring on the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1
Remove the service cover.
2
Connect the transmission wiring as follows:
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
a
b
X1M (A1P)
F1
Q2
F2
F1
Q1
F2
TO MULTI
UNIT
TO OUT/D
TO IN/D
a
Use the conductor of sheathed wire (2 wire) (no polarity)
b
Terminal board (field supply)
3
Connect the power supply as follows:
3N~50 Hz
380-415 V
L1 L2 L3
L1 L2 L3
N
X1M
a
b
c
a
Earth leakage circuit breaker
b
Fuse
c
Power supply cable
4
Fix the cables (power supply and transmission wiring) with
cable ties.
a
a
b
X1M
X1M
(A1P)
a
a
a
Cable tie
b
Attachment plate
X1M
Power supply
X1M (A1P)
Transmission wiring
5
Route the wiring through the frame and connect it to it.
Routing through
the frame
Choose one of the 3 possibilities:
a
b
a
b
a
b
2
3
1
a
Power supply cable
b
Transmission wiring cable
Connecting to the
frame
When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.
When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.
a b c
d
e
A B
A
Inside of the outdoor unit
B
Outside of the outdoor unit
a
Wire
b
Bush
c
Nut
d
Frame
e
Hose
6
Reattach the service cover.
7
Connect an earth leakage circuit breaker and fuse to the power
supply line.