Installation and operation manual
48
RXYQQ8~20T7Y1B
VRV IV System Air Conditioner
4P345099-1 – 2013.04
4
Calculate the refrigerant density taking the volume of the room
where the indoor unit is installed and the adjacent room.
Install ventilation openings in the door of adjacent rooms until
the refrigerant density is smaller than the maximum
concentration level.
19. Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
20. Unit specifications
20.1. General technical specifications
INFORMATION
For technical and electrical details of multi unit
combinations, see technical engineering data.
RXYQQ8 RXYQQ10 RXYQQ12 RXYQQ14
Casing material
Painted galvanised steel
Dimensions h x w x d
(mm)
1685x930x765
1685x1240
x765
Weight
187
194
305
Operation range
• cooling (min./max.)
(°C)
–5/43
• heating (min./max.)
(°C)
–20/21
Cooling
(a)
• capacity
(kW)
22.4
28.0
33.5
40.0
• EER
4.30
3.84
3.73
3.64
Heating
(b)
• capacity
(kW)
25.0
31.5
37.5
45.0
• COP
4.54
4.27
4.12
4.02
PED
• category
2
• Most critical part
Accumulator
• PS*V
(bar*l)
325
415
Maximum number of indoor
units connected
(c)
64
Heat exchanger
• type
cross fin
• treatment
anti corrosion
Fan
• type
propeller
• quantity
1
2
• air flow rate
(d)
(m
3
/min)
162
175
185
223
• motor
1
2
• model
brushless DC
• output/pcs
(W)
750
Compressor
• quantity
1
2
• model
inverter
• type
hermetically sealed scroll compressor
• crankcase heater
(W)
33
Sound level (nominal)
(e)
• sound power
(f)
(dBA)
78
79
81
• sound pressure
(g)
(dBA)
58
61
Refrigerant
• type
R410A
• charge (factory)
(kg)
5.9
6
6.3
10.3
Refrigerant oil
Synthetic (ether) oil
Safety devices
• High pressure switch
• Fan driver overload protector
• Inverter overload protector
• PC board fuse
(a) Nominal cooling capacities are based on indoor temperature 27°C DB and
19°C WB, outdoor temperature 35°C DB, equivalent refrigerant piping: 5 m, level
difference: 0 m.
(b) Nominal cooling capacities are based on indoor temperature 20°C DB, outdoor
temperature 7°C DB and 6°C WB, equivalent refrigerant piping: 5 m, level
difference: 0 m.
(c) Actual number of units depends on the connection ratio restriction for the system
(50%
≤
CR
≤
130%).
(d) Nominal at 230 V.
(e) Sound values are measured in a semi-anechoic room.
(f) Sound power level is an absolute value that a sound generates.
(g) Sound pressure level is a relative value depending on the distance and acoustic
environment. For more details, refer to sound level drawings in the technical data
book.
RXYQQ16 RXYQQ18 RXYQQ20
Casing material
Painted galvanised steel
Dimensions h x w x d
(mm)
1685x1240x765
Weight
305
314
Operation range
• cooling (min./max.)
(°C)
–5/43
• heating (min./max.)
(°C)
–20/21
Cooling
(a)
• capacity
(kW)
45.0
50.0
56.0
• EER
3.46
3.40
3.03
Heating
(b)
• capacity
(kW)
50.0
56.0
63.0
• COP
3.91
3.89
3.71
PED
• category
2
• Most critical part
Accumulator
• PS*V
(bar*l)
415
492.5
Maximum number of indoor
units connected
(c)
64
Heat exchanger
• type
cross fin
• treatment
anti corrosion
Fan
• type
propeller
• quantity
2
• air flow rate
(d)
(m
3
/min)
260
251
261
• motor
2
• model
brushless DC
• output/pcs
(W)
750
Compressor
• quantity
2
• model
inverter
• type
hermetically sealed scroll
compressor
• crankcase heater
(W)
33
Sound level (nominal)
(e)
• sound power
(f)
(dBA)
86
88
• sound pressure
(g)
(dBA)
64
65
66
Refrigerant
• type
R410A
• charge (factory)
10.4
11.7
11.8
Refrigerant oil
Synthetic (ether) oil
Safety devices
• High pressure switch
• Fan driver overload protector
• Inverter overload protector
• PC board fuse
RXYQQ8 RXYQQ10 RXYQQ12 RXYQQ14