3
|
Troubleshooting
Service manual
35
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
126].
Possible cause:
Faulty main PCB.
2
Perform a check of the outdoor unit fan motor. See
135].
Possible cause:
Faulty outdoor unit fan motor.
3
Check if the power supply is compliant with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (power supply MUST be within
range of nominal operating voltage ±4%),
▪
Power drop,
▪
Short circuit.
4
Clean the outdoor heat exchanger. See
222].
Possible cause:
Dirty outdoor heat exchanger.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.27 L4-00 – Outdoor unit: Malfunction of inverter radiating fin temperature rise
Trigger
Effect
Reset
Radiating fin thermistor
measures a too high
temperature.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outdoor unit fan motor. See
135].
Possible cause:
Faulty outdoor unit fan motor.
2
Check if the power supply is compliant with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (power supply MUST be within
range of nominal operating voltage ±4%),
▪
Power drop,
▪
Short circuit.
3
Perform a check of the main PCB. See
126].
Possible cause:
Faulty main PCB.