3
|
Troubleshooting
Service manual
33
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
3.5.22 H8-00 – Outdoor unit: Malfunction of compressor input system
Trigger
Effect
Reset
DC voltage or current
sensor abnormality based
on the compressor
running frequency and
the input current.
Unit will NOT stop
operating.
Automatic reset when
compressor runs normally
for 60 minutes.
If the error re-occurs too
soon: unit will stop
operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
126].
Possible cause:
Faulty main PCB.
2
Perform a check of the compressor. See
57].
Possible cause:
Faulty compressor or miswiring of the compressor power
supply cable.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.23 H9-00 – Outdoor unit: Malfunction of outdoor air thermistor
Trigger
Effect
Reset
Outdoor air thermistor
input is out of range.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outdoor air thermistor. See
195].
Possible cause:
Faulty ambient air thermistor.
2
Perform a check of the main PCB. See
126].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.