3
|
Troubleshooting
Service manual
18
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
1
Check for improper combination of the indoor unit and the outdoor unit. See
the combination table in the Databook for more information.
2
Perform a check of the power supply, connections, wiring,… between the
outdoor unit and the indoor unit. See
Possible cause:
Faulty wiring between the outdoor unit and the indoor unit.
3
Check if the power supply is compliant with the regulations. See
209].
Possible cause:
▪
Faulty or disturbance of the power supply (power supply MUST be within
range of nominal operating voltage ±4%),
▪
Power drop,
▪
Short circuit.
4
Perform a check of the indoor unit main PCB. See
Possible cause:
Faulty indoor unit main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.2 A5-00 – Outdoor unit: High pressure peak cut / freeze protection problem
Trigger
Effect
Reset
During cooling operation,
indoor heat exchanger
temperature is below 0°C
(freeze‑up protection
control).
Unit will stop operating.
Automatic reset when
temperature is within
range.
During heating operation,
indoor heat exchanger
temperature is above
65°C (heating peak‑cut
control).
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check for objects near the indoor unit that may block the airflow. See
Possible cause:
Airflow of the indoor unit is blocked.
2
Clean the air filter of the indoor unit(s). See
Possible cause:
Faulty or dirty air filter.
3
Clean the indoor unit heat exchanger. See
222].
Possible cause:
Dirty indoor unit heat exchanger.
4
Perform a check of the indoor unit heat exchanger thermistor. See