Daikin RXS20K3V1B Installation Manual Download Page 15

English

8

6. 

Refilling the refrigerant

Check the type of refrigerant to be used on the machine nameplate.

Precautions when adding R410A

Fill from the gas pipe in liquid form.

It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon attached” displayed on it.)

Filling a cylinder with an attached siphon

Stand the cylinder upright when filling.

There is a siphon pipe inside, so the 

cylinder need not be upside-down to fill with 
liquid.

Filling other cylinders

Turn the cylinder upside-down 

when filling.

• Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

3

5

6

2

1

4

Please fill in with indelible ink, 

 

1

  the factory refrigerant charge of the product, 

 

2

  the additional refrigerant amount charged in the field and

 

1  +  2

  the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by 
the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: 

R410A

GWP

(1)

 value: 

1975

  

(1) 

GWP = global warming potential 

1

  factory refrigerant charge of the 

product: 
see unit name plate 

2

  additional refrigerant amount 

charged in the field 

3

  total refrigerant charge 

4

  Contains fluorinated greenhouse 

gases covered by the Kyoto 
Protocol

5

  outdoor unit

6

  refrigerant cylinder and manifold 

for charging

The filled out label must be adhered in the 
proximity of the product charging port (e.g. 
onto the inside of the stop valve cover).

NOTE

National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official 
national language on the unit. Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit.
Sticking instructions are illustrated on the backside of that label.

Standby Electricity Saving

The standby electricity saving function turns off power supply to the outdoor unit and sets the indoor unit 

into standby electricity saving mode, thus reducing the power consumption of the air conditioner.

The standby electricity saving function works on the following indoor units.

For all models after the FTXS20/25/35J type

CAUTION

• 

The standby electricity saving function cannot be used for models other than the specified ones.

 

Procedure for turning on standby electricity saving 

function

1) Check that the main power supply is turned off. Turn it off if 

has not been turned off.

2) Remove the stop valve cover.
3) Disconnect the selective connector for standby electricity 

saving.

4) Turn on the main power supply.

1

2

3

1

2

3

Standby electricity saving 
function off.

Standby electricity saving 
function on.

The standby electricity saving function is turned off before shipping.

CAUTION

• Before connecting or disconnecting the selective connector for standby electricity saving, make sure that the main power 

supply is turned off.

• The selective connector for standby electricity saving is required if an indoor unit other than the above applicable ones is connected.

01_EN_3P297037-2D.indd   8

11/1/2012   11:04:43 AM

Summary of Contents for RXS20K3V1B

Page 1: ...ation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie Split R410A Manuale dinstallazione Serie Multiambienti R410A R410A Manual de Instala o S rie split R410A R410...

Page 2: ...e 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 12E Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 RXS20J2V1B RXS25J2V1B RXS35J2V1B RKS20J2V1B RKS25J2V1B RKS3...

Page 3: ...ES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB65451 3 RXS20K2V1B RXS25K2V1B Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N20 09 2011 DEKRA Certification B...

Page 4: ...meda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan RXS20K2V1B RXS25K2V1B 3SB65451 4 Shinri Sada Manager Quality Control Department 3SB65451 4 fm Page 1 Thursday October 27 2011 4 49 P...

Page 5: ...AIKIN TCF 015 P7 07 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 14D Shinri Sada Manager Quality Control Department RXS20K3V1B RXS25K3V1B Machinery 2006 42 EC Electromagnetic Comp...

Page 6: ...5 2 40 DAIKIN TCF 015 P9 09 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 18F Shinri Sada Manager Quality Control Department RXS35K2V1B Machinery 2006 42 EC Electromagnetic Compati...

Page 7: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM...

Page 8: ...terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for...

Page 9: ...m television and radio sets This is to prevent interference to images and sounds Noises may be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other p...

Page 10: ...ove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve cover Insert the upper part of the stop valve cover into the outdoor unit to install Tighten the...

Page 11: ...the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts unt...

Page 12: ...lifetime The drying material may dissolve and damage the system Incomplete flaring may cause refrigerant gas leakage 4 Refrigerant piping work CAUTION Use the flare nut fixed to the main unit To preve...

Page 13: ...52W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and...

Page 14: ...nifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge...

Page 15: ...nd manifold for charging The lled out label must be adhered in the proximity of the product charging port e g onto the inside of the stop valve cover NOTE National implementation of EU regulation on c...

Page 16: ...peration press the switch SW1 1 2 3 The selective connector for standby electricity saving in use with standby electricity saving function turned off Push Screwdriver Power supply terminal block Force...

Page 17: ...Earth leakage circuit breaker Earth Inter unit wire 4 core 1 5mm or more H05RN Firmly x the wires with the terminal screws Outdoor unit Indoor unit Power supply 50Hz 220 240V Firmly x the wires with t...

Page 18: ...r in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off...

Page 19: ...Two dimensional bar code is a code for manufacturing 3P297037 2D M12B067A 1210 HT 00_CV_3P297037 2D indd 2 11 1 2012 11 01 11 AM...

Reviews: