• Split Sky Air • Outdoor Units
9
• Outdoor Units • R-410A • RXS-G2V1B
3
Electrical data
3
3
Representative unit combination
Power supply
Comp.
OFM
IFM
Indoor unit
Outdoor unit
Hz-volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FFQ25B8V1B
RXS25G2V1B
50 - 220
50 - 230
50 - 240
Max. 50Hz 264V
Min. 50Hz 198V
9.75
10
55
3.7
23
0.16
55
0.6
3.5
3.4
3D055010B
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps (A)
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on
the document title of your choice.
3D055009B
Representative Unit Combination
Power Supply
Comp
OFM
IFM
Indoor Unit
Outdoor Unit
Hz-Volts
Voltage Range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTXS35G2V1B
RXS35G2V1B
50 - 230
Max. 50Hz 264V
Min. 50Hz 198V
9.75
10
65
3.9
50
0.23
23
0.15
3.7
S
IMBOLS
N
OTES
MCA : Min. circuit amps.
(A)
1
RLA is based on the following conditions.
Indoor temp. 27C°DB/19°CWB
Outdoor Temp. 35°CDB.
2
Maximum allowable voltage variation between phases is 2%.
3
Select wire size based on the lager value of MCA.
4
Instead of fuse, use circuit breaker.
MFA : Max. Fuse Amps.
(A)
RLA
: Rated Load Amps.
(A)
OFM : Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
(A)
W
: Fan Motor Rated Output
(W)
RHz
: Rated Operated Frequency
(Hz)