Field Setting
Si34-603
82
Test Operation
3.1.4
Setting Contents and Code No.
– VRV Indoor Unit
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked
are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. “88” may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to “Equipped”, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
VRV
system
indoor
unit
settings
Mode
No.
Note 2
Setting
Switch
No.
Setting Contents
Second Code No.(Note 3)
01
02
03
04
10(20)
0
Filter contamination heavy/
light (Setting for display
time to clean air filter)
(Sets display time to clean
air filter to half when there is
heavy filter contamination.)
Super
long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200
hrs.
Approx.
100
hrs.
1
Long life filter type
Long life filter
Super long life
filter
—
—
2
Thermostat sensor in remote controller
Use
No use
—
3
Display time to clean air filter
calculation (Set when filter sign is not
to be displayed.)
Display
No display
—
12(22)
0
Optional accessories output selection
(field selection of output for adaptor for
wiring)
Indoor unit
turned ON by
thermostat
Operation output
Malfunction
output
1
ON/OFF input from outside (Set when
ON/OFF is to be controlled from
outside.)
Forced OFF
ON/OFF control
External
protection device
input
—
2
Thermostat differential changeover
(Set when remote sensor is to be
used.)
1°C
0.5°C
—
—
3
OFF by thermostat fan speed
LL
Set fan speed
—
—
4
Automatic mode differential (automatic
temperature differential setting for VRV
system heat recovery series cool/heat)
01:0
02:1
03:2
04:3
05:4
06:5
07:6
08:7
5
Power failure automatic reset
Not equipped
Equipped
—
—
13(23)
0
High air outlet velocity
(Set when installed in place with ceiling
higher than 2.7 m.)
N
H
S
—
1
Selection of air flow direction
(Set when a blocking pad kit has been
installed.)
F (4 directions)
T (3 directions)
W (2 directions)
—
3
Air flow direction adjustment (Set at
installation of decoration panel.)
Equipped
Not equipped
—
4
Field set air flow position setting
Draft prevention
Standard
Ceiling Soiling
prevention
—
5
Field set fan speed selection
(fan speed control by air discharge
outlet for phase control)
Standard
Optional
accessory 1
Optional
accessory 2
—
15(25)
1
Thermostat OFF excess humidity
Not equipped
Equipped
—
—
2
Direct duct connection
(when the indoor unit and heat reclaim
ventilation unit are connected by duct
directly.)
∗
Note 6
Not equipped
Equipped
—
—
3
Drain pump humidifier interlock
selection
Not equipped
Equipped
—
—
5
Field set selection for individual
ventilation setting by remote controller
Not equipped
Equipped
—
—
6
Field set selection for individual
ventilation setting by remote controller
Not equipped
Equipped
—
—
Summary of Contents for RXMQ4 5 6PVE
Page 11: ...Introduction Si34 603 x...
Page 45: ...Specifications Si34 603 34 Specifications...
Page 56: ...Si34 603 Refrigerant Circuit Refrigerant Circuit 45 C 3D052627A A P G N M D D O H F S E T...
Page 121: ...Field Setting Si34 603 110 Test Operation...
Page 222: ...Si34 603 Wiring Diagrams Appendix 211 2 1 2 Cooling Only RXMQ4 5 6PVE 3D051731C...
Page 223: ...Wiring Diagrams Si34 603 212 Appendix 2 2 Field Wiring RX Y MQ4 5 6PVE 3D052597...
Page 224: ...Si34 603 Wiring Diagrams Appendix 213 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Page 225: ...Wiring Diagrams Si34 603 214 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 226: ...Si34 603 Wiring Diagrams Appendix 215 FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Page 227: ...Wiring Diagrams Si34 603 216 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 230: ...Si34 603 Wiring Diagrams Appendix 219 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561A...
Page 231: ...Wiring Diagrams Si34 603 220 Appendix FXMQ40MA 50MA 63MA 80MA 100MA 125MAVE 3D039620B...
Page 232: ...Si34 603 Wiring Diagrams Appendix 221 FXHQ32MA 63MA 100MAVE 3D039801D...
Page 233: ...Wiring Diagrams Si34 603 222 Appendix FXAQ20MA 25MA 32MAVE 40MA 50MA 63MAVE 3D034206C...
Page 235: ...Wiring Diagrams Si34 603 224 Appendix FXUQ71MA 100MA 125MAV1 3D044973A...
Page 236: ...Si34 603 Wiring Diagrams Appendix 225 BEVQ71MA 100MA 125MAVE 3D044901B...
Page 241: ...Example of Connection Si34 603 230 Appendix...
Page 247: ...Method of Replacing the Inverter s Power Transistors Modules Si34 603 236 Appendix...
Page 262: ...Service Manual R 410A RX Y MQ4 5 6PVE Si34 603 Printed in Japan 07 2006 AK July...